AK-PC 781
Capacity
controller RS8GG602 © Danfoss 2015-03
121
Regulation limitations of the receiver pressure
Note
The PI regulation of the receiver pressure must have space to
regulate without restrictions.
This means that there should be sufficient space for the PI regula-
tion to move around the reference, i.e. at least 2-3 bars – both over
and below the reference.
The value is very dependent on the tuning of the PI regulation
and the system dynamics.
An example may be a 40-bar plant in which the receiver's refer-
ence pressure is set to 35 bars. Here the system can interfere
with normal regulation because the high pressure limit is very
stringent.
COP optimisation
As a transition to this receiver control, a separate compressor
control can be installed, which will optimise COP via parallel
compression.
This function is described on the next page.
Receiver control
The receiver pressure can be controlled so that it is kept at a set
reference point. This control requires the installation of an CCM
valve a (ETS valve) and a pressure transmitter. It is possible to
regulate using two parallel valves.
If only monitoring and not control is required, the valve should
not be installed. Install the pressure transmitter only.
There are two safety functions for the receiver. They are only avail-
able for gas-cooled regulation.
A P-belt must be installed to be able to regulate the function, but
both are standard set to zero, which makes the function inactive.
Receiver pressure's max. limit
Set a max. receiver pressure. If the controller register receiver
pressure beyond the set value, the ICMTS valve will be closed.
The opening degree will be linear through the p-band so that the
ICMTS valve will be closed by pressing 'set max. receiver pressure'
plus 'set-p-band'.
If the valve's opening degree is set to a limited value and cannot
be fully closed, the set opening degree value will be at the pres-
sure 'set max. receiver pressure' plus 'set p-band'.
As such, gas can still be sent through the valve.
Receiver pressure's min. limit:
A minimum receiver pressure limit can be set. If the controller
register receiver pressure below the set value, the ICMTS valve will
be opened. The opening degree will be linear through the p-band,
and the maximum permitted opening degree of the ICMTS will be
present by pressing 'set min. receiver pressure' minus 'set-p-band'.
If the setting of the valve's opening degree is limited and it cannot
be fully opened, the set opening degree value will be at the pres-
sure 'set min. receiver pressure' minus 'set p-band'.
Hot gas dump
The controller has a function that can turn on the hot gas to the
receiver if the pressure becomes lower than the set value. The hot
gas will shut off again when the pressure exceeds the difference.
Stop of compressors
If the compressors are stopped via the function "External com-
pressor stop", the reference for the receiver control will be to the
setting "Max. receiver pressure".
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...