108
Capacity
controller RS8GG602 © Danfoss 2015-03
AK-PC 781
Safety relays
The controller can manage the oil supply to the compressors
during normal regulation. However if the compressors are force
controlled, this will be done outside the normal regulation. To
avoid compressor damages, a safety relay can be incorporated in
the control circuit so the controller can cutout the compressor if
the oil supply is absent during forced control.
The function "Safety relay" can be selected under setup and wiring
should be done as shown.
The safety relay is connected during
normal operating conditions
Oil management
Principle
The controller turns on the oil flow for e.g. 1 second. The system
then pauses while the oil once again settles. This is repeated a
certain number of times, which will be determined by the plant
and control principles.
The pulse time, pause time and number of pulses can be adjusted.
The system can be controlled by signal from:
• Level switch on compressor
• Level switch on oil separator
• Level switch on oil receiver
• Pressure transmitter on oil receiver
• In special circumstances the pulse counter can also be used to
control, but this is not energy efficient.
Examples of oil circuits
Control principle for compressor
A compressor that is shut down does not receive any oil.
When the compressor is in operation, a signal from the compres-
sors oil-level switch is expected. When the signal is given, the
following process is carried out:
- Adjustable delay time, re-started in case of chatter.
- Oil injection commences after delay time sequence.
- The solenoid valve follows the pulse process and the oil is
injected. Pulse time, period time and the total number of pulses
are set for the current plant.
- After the defined number of pulses, the oil injection is stopped
again. If the level switch registers a stable oil signal before the
sequence of the defined number of pulses finishes, the remain-
ing pulses are omitted.
- If the level switch registers a lack of oil when the last pulse has
stopped, the compressor will be shut down and an alarm will be
given. If the oil level is deemed to be OK again, the alarm will be
cancelled and the compressor can restart.
If an OK on oil level is absent, the compressor will stop and can
then only be manually started using the reset function.
- Advanced stop. (allows pulses when the compressor is stopped)
This function divides the pulse count by two. The compressor will
then stop, after which the remaining pulses will be made.
One oil separator and
one oil receiver
One oil separator
One oil separator per
compressor
One oil separator per
compressor and
common oil receiver
Both high and low pressure and
common oil receiver
(+ oil separator)
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...