68
Capacity
controller RS8GG602 © Danfoss 2015-03
AK-PC 781
5. Setup values for tap water cir-
cuits
Press the
+
-button to go on to the
next page
6. Setup values for heating circuit
5 -
Tap water circuits
(settings are available only when the
refrigerant selected is CO2, and shall be regulated on a
circuit for tap water).
Control mode
: Here the regulation of the circuit can be
started (auto) and stopped (off).
Reference
: The required temperature for the sensor Stw8
can be set here.
Thermostat band
: The acceptable temperature variation
around the reference:
Control signal
. . Choose between:
Stw8:
if regulation shall be done using only this sensor.
S4-S3:
(and a Delta T value) if the controller shall regulate
using this temperature difference, until the Stw8 refer-
ence is met. (During S4-S3 regulation, the pump must
always be speed-regulated).
Stw8 + Stw8A:
if two temperature sensors are installed in
the hot water receiver.
Variable speed:
Here the pump type is selected. Either
variable speed or on/off.
Advanced settings:
The following options are made avail-
able:
Flow switch:
Must normally be selected for safety purposes
Kp:
Amplification factor
Tn:
Integration time
Min. pump speed:
Pump speed for start/stop
Max. pump speed:
The pump's max. permissible speed
Flowswitch delay
: Duration of stable signal before the new
status is used in the regulation.
6 -
Heat reclaim circuits
(settings are available only when
the refrigerant chosen is CO2, and regulation shall be
done using a circuit for heating).
Control mode
: Here the regulation of the circuit can be
started (auto) and stopped (off).
Reference
: Here the required temperature of sensor Shr8
(or Shr4) is set.
Thermostat band
: The permissible temperature variation
around the reference:
Control signal
: Choose between:
Shr8:
if regulation shall be done using only this sensor.
S4-S3:
(and a Delta T value) if the controller shall regulate
using this temperature difference, until the Shr8 refer-
ence has been met.
Shr4:
regulation is done using this sensor, but Shr8 shall
also be installed. (During S4-S3 regulation or Shr4 regula-
tion the pump shall always be speed-regulated).
Variable speed:
Here the pump type is selected. Either
variable speed or on/off.
Heat consumers
: (Only when the condensation pressure
shall be increased during heat recovery). The number of
signals that can be received is set here. The signal can be
either 0-10 V or 0-5 V. (Settings under "Advanced" will be
used 0-100% for the signal).
Heat consumer filter
The highest of the received signals are made known over
this period
Additional heat output
The function will reserve a relay. The relay will pull in when
the signal for the heat removers reaches 95%.
Advanced settings
: The following options are made avail-
able:
Flow switch:
Must normally be selected for safety pur-
poses
Kp:
Amplification factor
Tn:
Integration time
Tc max HR:
Value at which the bypass of the gas cooler
will terminate.
HR PUMP CONTROL
Min. pump speed:
Pump speed for start/stop
Max. pump speed:
The pump's max. permissible speed
Pump stop limit:
Signal in % at which the pump is
stopped again
Pump start limit:
Signal in % at which the pump is started
HP CONTROL
Pgc HR min:
Basic reference for the pressure when exter-
nal voltage signal is received.
In our example we use the
settings shown
In our example we use the
settings shown
Configuration - continued
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...