80
Capacity
controller RS8GG602 © Danfoss 2015-03
AK-PC 781
Check configuration
1. Go to Configuration menu
2. Select I/O configuration
3. Check configuration of Digital Outputs
Press the
+
-button to go on to the next page
4. Check configuration of Digital Inputs
Configuration - continued
This control requires that the setup is locked
(Only when the setup is locked are all settings for in- and out-
puts activated.)
An error has occurred, if you see the fol-
lowing:
A
0 – 0
next to a defined function.
If a setting has reverted to 0-0, you must control
the setup again.
This may be due to the following:
• A selection has been made of a combination of
module number and point number that does
not exist.
•
The selected point number on the selected mod-
ule had been set up for something different.
The error is corrected by setting up the output
correctly.
Remember that the setup must be unlocked be-
fore you can change module and point numbers..
The settings are shown on a
RED
background.
If a setting has turned red, you must control the
setup again.
This may be due to the following:
• The input or the output has been set up; but the
setup has later been changed so that it should
no longer be applied.
The problem is corrected by setting
module
number to 0 and point number to 0.
Remember that the setup must be unlocked be-
fore you can change module and point numbers.
The setup of the digital
inputs appears as it is sup-
posed to according to the
wiring made.
The setup of the digital
outputs appears as it is sup-
posed to according to the
wiring made.
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...