![Danfoss ADAP-KOOL AK-PC 781 Design Manual Download Page 76](http://html1.mh-extra.com/html/danfoss/adap-kool-ak-pc-781/adap-kool-ak-pc-781_design-manual_3529520076.webp)
76
Capacity
controller RS8GG602 © Danfoss 2015-03
AK-PC 781
Press the
+
-button to go on to
the next page.
5. Configuration of Analog
outputs
Press the
+
-button to go on to
the next page
6. Configuration of Analog
Input signals
Configuration - continued
5 - Analog outputs
The possible signals are
the following:
0 -10 V
2 – 10 V
0 -5 V
1 – 5V
Stepper output
Stepper output 2
Stepper user defined: See
section "Miscellaneous"
6 - Analog inputs
The possible signals are
the following:
Temperature sensors:
• Pt1000
• PTC 1000
Pressure transmitters:
• AKS 32, -1 – 6 bar
• AKS 32R, -1 – 6 bar
• AKS 32, - 1 – 9 bar
• AKS 32R, -1 – 9 bar
• AKS 32, - 1 – 12 bar
• AKS 32R, -1 – 12 bar
• AKS 32, - 1 – 20 bar
• AKS 32R, -1 – 20 bar
• AKS 32, - 1 – 34 bar
• AKS 32R, -1 – 34 bar
• AKS 32, - 1 – 50 bar
• AKS 32R, -1 – 50 bar
• AKS 2050, -1 – 59 bar
• AKS 2050, -1 – 99 bar
• AKS 2050, -1 – 159 bar
• User defined (only
ratiometric, min. and max
value of the pressure
range must be set)
S4 Cold brine
Pctrl
Po suction pres.
Ss suction gas
Sd disch. temp.
Pc Cond. Pres.
S7 Warm brine
Sc3 air on
Ext. Ref. Signal
• 0 – 5 V,
• 0 -10 V
Olie receiver
HP control
Pgc
Prec
Sgc
Shp
Stw2,3,4,8
Shr2,3,4,8
HC 1-5
Heat recovery
Saux 1 - 4
Paux 1 - 3
Voltage input 1 - 5
• 0 -5 V,
• 0 -10 V,
• 1 – 5 V,
• 2 – 10 V
PI-in temp
PI-ref temp
PI- in voltage
PI-in pres.
PI-ref pres.
Function
Output
Module
Point
Type
Voltage signal for high pressure
valve, ICMTS
AO1
1
24
0-10 V
Stepper signal for by-pass valve, CCM
Step 1
3
9
CCM
Speed control, compressor
AO1
5
5
0 - 10 V
Speed control, gas cooler fan
AO2
5
6
0 - 10 V
Speed control, pump - tw
AO3
5
7
0 - 10 V
Speed control, pump - hr
AO4
5
8
0 - 10 V
Sensor
Input
Module
Point
Type
Disch. gas temperature - Sd
AI1
1
1
Pt 1000
Suction gas temperature - Ss
AI2
1
2
Pt 1000
Outdoor temp. - Sc3
AI3
1
3
Pt 1000
Thermostat sensor in plant room -
Saux1
AI5
1
5
Pt 1000
Suction pressure - Po
AI6
1
6
AKS 2050-59
Condenser pressure - Pc
AI7
1
7
AKS 2050-159
Refrigerant receiver, Prec-CO2
AI7
2
7
AKS 2050-159
Oil receiver, Prec-Oil
AI8
2
8
AKS 2050-159
Tap water temperature - Stw2
AI1
3
1
Pt 1000
Tap water temperature - Stw3
AI2
3
2
Pt 1000
Tap water temperature - Stw4
AI3
3
3
Pt 1000
Tap water temperature - Stw8
AI4
3
4
Pt 1000
Heat reclaim temperature Shr2
AI5
3
5
Pt 1000
Heat reclaim temperature Shr3
AI6
3
6
Pt 1000
Heat reclaim temperature Shr4
AI7
3
7
Pt 1000
Heat reclaim temperature Shr8
AI8
3
8
Pt 1000
Temp. gas cooler outlet Sgc
AI1
5
1
Pt 1000
Temp. by-pased gas Shp
AI2
5
2
Pt 1000
Gas cooler pressure Pgc
AI4
5
4
AKS 2050-159
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...