128
Capacity
controller RS8GG602 © Danfoss 2015-03
AK-PC 781
Display of suction pressure and condensing pressure
One to four separate displays can be connected to the controller.
Connection is accomplished by means of wires with plug
connections. The display may be placed in a control box front, for
example.
When a display is connected, it will show the value for what is indi-
cated in the setup. It can be:
compressors regulation sensor
P0 i temperature
P0 i bar-absolute
Pctrl bar-absolute
S4
Ss
Sd
Condensors regulation sensor
Tc
Pc bar-absolute
S7
Sgc
Shp
Pgc bar-absolute
Prec bar-absolute
Stw8
Shr8
Speed Compressor
Display
Primary readout *
Secondary readout
A
Regulation sensor suction
pressure
Regulation sensor con-
denser
B
Regulation sensor con-
denser
Regulation sensor suction
pressure
C
SS
None
D
SD
None
* The primary reading can be changed to other measurements, if required.
When (on plug A) a display with control buttons is chosen, a sim-
ple operation via a menu system can be performed in addition to
the display of suction pressure and condensing pressure:
If you want to see one of the values for what is given under "func-
tion" you should use the buttons in the following way:
1. Press on the upper button until a parameter is shown
2.Press on the upper or lower button and find the parameter you
want to read
3. Press on the middle button until the value of the parameter is
displayed.
After a short time, the display will return automatically to the
"Read out display".
No.
Function
Cond.
Suc-
tion
Pack
o57
Capacity settings for condenser
0: MAN, 1: OFF, 2: AUTO
x
x
o59
Capacity setting for suction group
0: MAN, 1: OFF, 2: AUTO
x
x
h15
High pressure. Setting of Pgc minimum
x
h16
High pressure. Setting of HP-control mode: Automatic /
manual
x
h17
High pressure. Manuel mode. Setting of valves opening
degree
x
h18
Heat recovery. Reference for Shr8-temperature
x
h19
Heat recovery. Setting of heat recovery control mode:
Automatic / off
x
o30
Refrigerant setting
x
x
x
058
Manual setting of condenser capacity
x
x
o60
Manual setting of suction capacity
x
x
o62
Select of predefined configuration
This setting will give a selection of predefined combina-
tions which at the same time establish the connections
points.. At the end of the manual an overview of options
and connection points is shown. After the configuration
of this function the controller will shut down and restart
x
x
x
o93
Lock of configuration
It is only possible to select a predefined configuration or
change refrigerant when the configuration lock is open.
0 = Configuration open
1 = Configuration locked
x
x
x
r12
Main switch
0: Controller stopped
1: Regulating
x
x
x
r23
Set point suction pressure
Setting of required suction pressure reference in °C
x
x
r24
Suction pressure reference
Actual reference temperature for compressor capacity
x
x
r28
Set point condenser
Setting of required condenser pressure in °C
x
x
r29
Condenser reference
Actual reference for temperature for condenser capacity
x
x
r57
Po evaporating pressure in °C
x
x
r86
Receiver control. Reference for Prec
x
r87
Receiver control. Setting of the receiver control mode :
Automatic / manual
x
r88
Receiver control. Manual mode. Setting of the valves
opening degree
x
t49
Hot water. Reference for Stw8-temperature
x
t50
Hot water. Setting of hot water control mode: Automatic
/ off
x
u16
Actual media temperature measured with S4
x
x
u21
Superheat in suction line
x
x
u44
Sc3 out door temperature in °C
x
x
u48
Actual regulation status on condenser
0: Power up
1: Stopped
2: Manuel
3: Alarm
4: Restart
5: Standby
6: Unloaded
7-9: Part loaded
10: Full loaded
11: Running
x
x
u49
Cut in condenser capacity in %
x
x
u50
Reference for condenser capacity in %
x
x
u51
Actual regulation status on suction group
0: Power up
1: Stopped
2: Manuel
3: Alarm
4: Restart
5: Standby
6-10: Status_RUN_Timer
11: Unloaded
12-14: Unloads cut-in
15: Full loaded
16: Running
x
x
u52
Cut in compressor capacity in %
x
x
u53
Reference for compressor capacity
x
x
u54
Sd discharge gas temperature in °C
x
x
u55
Ss Suction gas temperature in °C
x
x
u98
Actual temperature for S7 media sensor
x
x
u99
Pctrl pressure in °C (cascade pressure)
x
x
U01
Actual Pc condensing pressure in °C
x
x
AL1
Alarm suction pressure
x
x
AL2
Alarm condenser
x
x
- - 1
Initiation, Display is connected to output "A", (- - 2 =
output "B" etc.)
x
x
x
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...