AK-PC 781
Capacity
controller RS8GG602 © Danfoss 2015-03
63
Setup control of condenser
fans
1. Go to Configuration menu
2. Select Condenser fan control
3. Set control mode and reference
Press the
+
-button to go on to the
next page
4. Set values for capacity regulation
Configuration - continued
3 - PC reference
Control sensor
Pc: The condensing pressure PC is used for regulation
Sgc: The temperature at the outlet of the gas cooler (CO2
transcritical only)
S7: Media temperature is used for regulation
Reference Mode
Choice of condenser pressure reference
Fixed setting: Used if a permanent reference is required =
“Setting”
Floating: Used if the reference is changed as a function
of Sc3 the external temperature signal, the configured
"Dimensioning tm K"/"Minimum tm K" and the actual cut in
compressor capacity. (Liquid is recommended for CO2 and
heat recovery.)
Setpoint
Setting of desired condensing pressure in bar
Min. tm
Minimum average temperature difference between Sc3 air
and Pc condensing temperature with no load.
Dimensioning tm
Dimensioning average temperature differential between Sc3
air and Pc condensing temperature at maximum load (tm
difference at max load, typically 8-15 K).
Min reference
Min. permitted condenser pressure reference
Max reference
Max. permitted condenser pressure reference
4 - Capacity control
No of fans
Set number of fans.
Monitoring fan safety
Safety monitoring of fans. A digital input is used to monitor
each fan.
Capacity control mode
Select control mode for condenser
Step: Fans are step-connected via relay outputs
Step/speed: The fan capacity is controlled via a combination
of speed control and step coupling
Speed: The fan capacity is controlled via speed control
(frequency converter)
Speed 1.step: First fan speed controlled, rest step coupling
Fan speed type
VSD (and normal AC motors)
EC motor = DC controlled fan motors
VSD start speed
Minimum speed for start of speed control (Must be config-
ured higher than "VSD Min. Speed %")
VSD min Speed
Minimum speed whereby speed control is cut-out (low
load).
VSD safety monit.
Choice of safety monitoring of frequency converter. A digital
inlet is used for monitoring the frequency converter.
EC Start capacity
The regulation awaits this need to arise before supplying
voltage to the EC motor
EC voltage min
Voltage value at 0% capacity
EC voltage max
Voltage value at 100% capacity
EC Voltage abs. max
Permissible live voltage for EC motor (overcapacity)
Absolut max Tc
Max value for Tc.
If this Tc value is exceeded, the EC voltage
will be raised to the value in “EC Voltage abs. max.”
Control type
Choice of control strategy
P-band: The fan capacity is regulated via P-band control. The
P band is configured as "Proportional band Xp"
PI-Control: The fan capacity is regulated by the PI controller.
Continues
For your information the function
”Monitor fan safety” will require
an input signal from each fan.
In our example the condenser
pressure is controlled on the basis
of the Sgc and from Sc3 (floating
reference).
The settings shown here in the
display.
In our example we use a number of
fans that are all speed-controlled
in parallel.
The settings shown here in the
display.
Summary of Contents for ADAP-KOOL AK-PC 781
Page 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Page 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Page 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Page 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...