www.daisalux.com
21
LPS24
– USER MANUAL
8.2.1. System
8.2.1.1. General
Overview
OK
Main menu
OK
GENERAL
Vmains:
230 v
Vinter:
27.3 v
Ioutput:
4.3A
Contactor:
open
Communication:
USB
Gen
Bat
Rect Fails
Vmains
: Mains voltage at the unit’s input.
Vinter
: Device internal voltage.
Ioutput
: Current consumption at outputs
Contactor
: Current status of battery contactor (
open/closed
).
Communication
: Unit’s communication mode with a PC (
USB/ethernet/-
).
8.2.1.2. Battery
Overview
OK
Main menu
OK
Gen
>
BATTERY
Vbat:
27.2v
VbatInt:
13.7v
Ibat:
-10.3A
Temperature:
24.3ºC
Charge:
100% (20.0Ah)
Status:
ok
Gen
Bat
Rect Fails
Vbat
:
Battery voltage.
VbatInt
: Mid-battery voltage. To determine whether the two batteries are balanced
Ibat
: Battery charge/discharge current.
Temperature
: Temperature in the battery enclosure.
Charge
: Estimated battery charge level.
Status
: Reports on the battery status:
•
Fuse failure
: fault detected on fuse F2 or F3
•
Not symmetric
: if the batteries do not have similar voltages, this may indicate a
battery fault. Run a duration test to verify that it is correct
•
Wrong connected
: no battery connected to a device is detected, check fuses and
battery wiring
•
open
: battery open or in bad state
•
overvoltage
: battery voltage very high
•
undervoltage
: low battery voltage
•
OK
: battery correct