8.2.7. Appendix
8.2.7.1. Alert messages
When the device detects an alert, a pop-up is generated on the display with the error
message. The user can remove the pop-up by pressing the
OK
or
←
key.
Below is a list of the alerts available and an explanation.
Alert
Description
End of bat discharge log
A record indicating that the device has been in standby since reaching
the end of discharge
Battery is running down
The device detects that it has energy for less than 10 minutes
Input overvoltage
The device has detected a voltage on the input well above its nominal
voltage
System overload
The device has detected that the load connected is higher than its
maximum power
Mains failure
Mains failure on the unit’s input.
Remote mains failure
Mains failure in a remote mains detector associated with the device
Global siwtch on active
Active auxiliary switch on
DBR switch on active
Active DBR switch on
Internal voltage error
Voltage generated by the rectifier outside of range
Battery voltage error
Battery voltage out of range
Wrong battery temperature
Temperature in the battery compartment outside of range
Function test on course
The device is running a functional test
Duration test on course
The device is running a duration test
Capacity test on course
The device is running a capacity test
Circuit test on course
The device is running a circuit test
Duration test required
The duration test period has transpired without a test having been
performed. A test must be run to check the system’s duration
Function test failure
Fault detected in the last functional test
Duration test severe fail
A serious fault was detected during the last duration test (duration less
than 60% of the nominal duration)
Duration test light fail
A minor fault was detected during the last duration test (duration higher
than 60% and lower than 100% of the nominal duration)
Battery bad connected
Incorrectly connected battery
Battery open
Battery open or in bad state
Battery not symmetric
Batteries not symmetrical. Possible fault in a battery
Battery fuse failure
Fault in any of the battery fuses
Temperature sensor failure
Failure in the communication with the temperature probe
Output circuit failure
A circuit fault
Battery charge failure
Battery charge regulation fault
Rectifier failure
Failure in the rectifier
Electronic failure
Fault in the device’s electronics. Requires repair
Contactor open
Contactor open. Installation uncertain in the event of power failure.
Zoning on course
The device is running a zoning process
Shutting down …
The device is in standby
Command executed
User command executed
Password: 0000
Request the password required to edit the value or execute the order
Low security
The device estimates that the installation requires maintenance
Very low security
The device estimates that the installation is unsafe