www.daisalux.com
13
LPS24
– USER MANUAL
6.3.
Electrical connections
The wiring of the LPS centralised power unit is on the top of the same.
6.3.1. Power connection
Connect the power supply to terminals L, N and earth (PE).
6.3.2.Output circuits (OUT1, ..., OUT6)
The LPS system has six output circuits for monitoring the luminaires
(
ELC, “beacons”, non
-communicating
). These outputs must be pre-
8.2.4. Configuring the outputs
Each circuit supports a maximum output of 4 A of constant current
with intelligent protection against over-consumption and/or short
circuit. Caution: check that the total load does not exceed the system
output power. See
!
Check the compatibility of each luminaire connected to an
output circuit configured as “
beacons
”, as not all beacons allow
such functionality.
!
The ELC luminaires are not compatible with outlets configured
as “
beacon
”.
!
On the outputs defined as
beacons
, it is recommended not to adjust
the load over 3A (75% of the maximum 4A) to avoid possible over-
consumption on tests.
If low voltage (MBTS) is used to wire the luminaires there is no need for protection by
ground wire cable (PE). Observe the maximum lengths depending on the cable section
specified in
The luminaires are connected to the + and - terminals, which are duplicated in the
centralised power unit; i.e. it has two outputs for each circuit. To configure the luminaires
see