www.daisalux.com
15
LPS24
– USER MANUAL
6.3.3.2 Remote fault connection to several LPS24 devices
Another possible configuration would be that of several remote faults associated with an
LPS system, which through a dry output pre-configured into the next device in the
auxiliary input, this in turn would pass to the next LPS system, thus a remote fault would
be associated in series to several LPS systems.
The optional contact-free potential must be programmed according to the instruction, see
6.3.4. Dry contacts (CLP1, ..., CLP4)
There are four dry contacts, three of them fixed according to the EN 50171 standard and
the fourth configurable by the user.
Available options
Option details
Default configuration of
the contacts
1
2
3
4
Buzzer
System working
•
System in operation (not in standby)
x
Mains failure
•
Mains failure on the unit’s input
Local mains failure
•
Remote mains failure (not on the unit’s
input)
Communicated with a
PC
•
System with active communication with a
PC (Daisatest, WinCB or access to web
server)
Global switch on active
•
Device with active auxiliary switched on
DBR switch on active
•
Device with active DBR switched on
Zoning on course
•
Device running luminaire zoning
Battery is running
down
•
Alarm for next end of active discharge
Contactor open
•
Battery contactor open