• All service shall be performed by quali
fi
ed service personnel. This product must be in-
stalled and maintained in accordance with the applicable installation codes by a person
familiar with the construction operation of the product and the hazards involved.
• This product must be installed in accordance with the applicable installation codes and
ordinances.
• Before wiring to power supply, turn off electricity at fuse or circuit breaker.
• Disconnect A. C. power and unplug battery before servicing.
• Consult your local building code for approved wiring and installation.
• UL listed for wet locations (-20°C-50°C)
• Do not let power supply cord touch hot surfaces.
• Do not mount near gas or electric heater.
• Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Do not use this equipment for other than intended use.
• The AC voltage rating of this equipment is speci
fi
ed on the product label. Do not connect equipment to any other voltage.
1.
Use
fl
at he ad screwdriver to loosen the screws on the
LENSES (A)
.
2.
Remove lens, from sign, set aside.
3.
Remove
EXIT STENCIL (B)
from
FIXTURE FRAME (C)
, set aside.
4.
Drill or knockout appropriate knockouts on
BACK PLATE (M)
to
fi
t junction box mounting points.
5.
Drill or knock
o
ut holes in back plate for
fi
xture supply wire leads.
6.
Remove backing from self-adhesive
JUNCTION BOX GASKET (F)
and adhere to back plate.
7.
Route
fi
xture input wires through center hole of the back plate and make wiring connection. For 120V, use black and white wires and for 277V,
use red and white wires. WARNING: Properly insulate the unused lead with a wire nut (provided) or other approved means.
8.
Secure back plate to
JUNCTION BOX (J)
(
junction box and
hardware not included).
9.
Remove proper chevron(s) from the face plate as required. When removing chevrons it may be helpful to remove the color diffuser panel to
allow easier access to the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel once chevron(s)
have been removed.
10.
Connect battery to lamp board (see wiring diagrams on page 3).
WET LOCATION LED COMBO EXIT & EMERGENCY LIGHT
NOTE
:
Max mounting height is 20 ft to achieve at least 1 ft-candle of illuminance in emergency mode.
WALL MOUNT INSTALLATION
WARNING:
RISK OF ELECTRIC SHOCK- NEVER CONNECT TO, DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
WARNING:
FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT
PROPERTY DAMAGE - For your protection, read and follow these warnings and instructions
carefully before installing or maintaining this
equipment. These instructions do not attempt to cover all installation and maintenance situations.
If you do not understand these instructions or
additional information is required, contact Lithonia Lighting or your local Lithonia Lighting distributor.
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
PAGE:
1
of
3
11. Secure face plate and back plate to the
fi
xture frame.
12. Secure lens to
fi
xture and securely torque screws.
13. Apply continuous AC power. Unit can be tested by holding the magnet (provided) near the LED indicator (where it’s marked as “Magnetic Test Switch”).
14. Magnet needs to be retained by building owner (or maintenance personnel) to perform monthly/annual inspections.
INSTALLATION INSTRUCTIONS for Lithonia Lighting WLTC models
CONDUIT ENTRY
1.
Drill a ¾” hole through the desired conduit entry knock out located on the top or side of the frame of the sign.
2.
Route the AC input conduit into housing.
3.
All conduit connections must use UL LISTED and SUITABLE FOR WET LO
C
ATION parts.
4. To finish installation of fixture, reference Wall, Ceiling or End Mount instructions.