Lithonia Lighting WLTC Series Installation Instructions Download Page 2

INSTALLATION INSTRUCTIONS

CEILING OR END MOUNT INSTALLATION

1.

Use flat head screwdriver to loosen the screws on the LENSES (A).

2.

Remove lens, from sign, set aside.

3.

Remove 

EXIT STENCIL (B)

 from 

FIXTURE FRAME (C)

, set aside.

4.

Drill ¾” holes through the desired mounting knockouts located on the 

fi

xture

 frame. For ceiling mount, knockouts will be located on the top of

 

the

 fixture

 frame. For wall mount, knockouts will be located on the side of the 

fixture

 frame.

5.

Using provided hardware, thread 

NUTS (D)

 onto 

PIPE NIPPLES (E)

. Slide pipe nipples through canopy holes.

6.

Remove backing from self adhesive 

JUNCTION BOX GASKET (F)

 and adhere to back of 

MOUNTING PLATE (G)

. Remove back-

ing from self adhesive 

PIPE THREAD GASKET (H)

 and adhere to front of 

MOUNTING CANOPY (I)

.

7.

Place screws (provided) in holes on the mounting canopy.

8.

Route fixture input wires through knockout in fixture frame, pipe nut and metal mounting plate.

9.

Make wiring connection. For 120V, use black and white wires and for 277V, use red and white wires. 

WARNING:

 Properly insulate the

 

unused

 

lead with a wire nut (provided) or other approved means.

10.

Push wire connections into the 

J-BOX (J)

 

(junction box not included).

 Secure mounting plate to junction box (hardware not included).

11.

Secure the canopy to the steel mounting plate with screws installed in step 7.

12.

Place pipe nipple through the mounting hole of the fixture frame until the gasket is touching the frame. Thread a second nut onto the pipe

 

nipple on the inside of the fixture frame to lock the canopy into place. Once canopy is locked into position there will not be any side-to-side

 

movement of the canopy.

13.

Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier access to

 

the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel once chevron(s) have been removed.

14.

Connect battery to lamp board (see wiring diagrams on next page).

15.

Secure face plate(s) to the fixture frame.

16.

Secure lens to 

fixture and securely

 torque screws.

17.

Apply continuous AC power. Unit

 

can be tested by holding the 

MAGNET (K)

 

(provided)

 near the LED indicator

(where it’s marked as “Magnetic Test

 

Switch”).

18.

Magnet needs to be retained by

 

building owner (or maintenance

 

personnel) to perform monthly/annual inspections. 

SAVE THESE INSTRUCTIONS

and deliver to owner after installation

PAGE: 

2

 of 

3

Ceiling Mount

End Mount

K

PARTS LIST 

A)

Lens(es)*

B)

Exit Stencil(s)*

C)

Fixture Frame

D)

Nuts (2)

E)

Pipe Nipples (2)

F)

Junction Box Gasket

G)

Mounting Plate

H)

Pipe Thread Gasket

I)

Mounting Canopy

J)

Junction Box**

K)

Magnet 

*1 for single-face or 2 for

 

double-face

**Junction Box not included

A

B

C

D

E

F

G

H

I

J

M

A

A

B

C

D

M

A

E

H

I

F

G

J

Reviews: