INSTALLATION INSTRUCTIONS
CEILING OR END MOUNT INSTALLATION
1.
Use flat head screwdriver to loosen the screws on the LENSES (A).
2.
Remove lens, from sign, set aside.
3.
Remove
EXIT STENCIL (B)
from
FIXTURE FRAME (C)
, set aside.
4.
Drill ¾” holes through the desired mounting knockouts located on the
fi
xture
frame. For ceiling mount, knockouts will be located on the top of
the
fixture
frame. For wall mount, knockouts will be located on the side of the
fixture
frame.
5.
Using provided hardware, thread
NUTS (D)
onto
PIPE NIPPLES (E)
. Slide pipe nipples through canopy holes.
6.
Remove backing from self adhesive
JUNCTION BOX GASKET (F)
and adhere to back of
MOUNTING PLATE (G)
. Remove back-
ing from self adhesive
PIPE THREAD GASKET (H)
and adhere to front of
MOUNTING CANOPY (I)
.
7.
Place screws (provided) in holes on the mounting canopy.
8.
Route fixture input wires through knockout in fixture frame, pipe nut and metal mounting plate.
9.
Make wiring connection. For 120V, use black and white wires and for 277V, use red and white wires.
WARNING:
Properly insulate the
unused
lead with a wire nut (provided) or other approved means.
10.
Push wire connections into the
J-BOX (J)
(junction box not included).
Secure mounting plate to junction box (hardware not included).
11.
Secure the canopy to the steel mounting plate with screws installed in step 7.
12.
Place pipe nipple through the mounting hole of the fixture frame until the gasket is touching the frame. Thread a second nut onto the pipe
nipple on the inside of the fixture frame to lock the canopy into place. Once canopy is locked into position there will not be any side-to-side
movement of the canopy.
13.
Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier access to
the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel once chevron(s) have been removed.
14.
Connect battery to lamp board (see wiring diagrams on next page).
15.
Secure face plate(s) to the fixture frame.
16.
Secure lens to
fixture and securely
torque screws.
17.
Apply continuous AC power. Unit
can be tested by holding the
MAGNET (K)
(provided)
near the LED indicator
(where it’s marked as “Magnetic Test
Switch”).
18.
Magnet needs to be retained by
building owner (or maintenance
personnel) to perform monthly/annual inspections.
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
PAGE:
2
of
3
Ceiling Mount
End Mount
K
PARTS LIST
A)
Lens(es)*
B)
Exit Stencil(s)*
C)
Fixture Frame
D)
Nuts (2)
E)
Pipe Nipples (2)
F)
Junction Box Gasket
G)
Mounting Plate
H)
Pipe Thread Gasket
I)
Mounting Canopy
J)
Junction Box**
K)
Magnet
*1 for single-face or 2 for
double-face
**Junction Box not included
A
B
C
D
E
F
G
H
I
J
M
A
A
B
C
D
M
A
E
H
I
F
G
J