6.12 Fan Motor Connector Check (Signal Cable)
CHECK 17
Resistance measuring points and judgment criteria.
FXMQ40PB, FXAQ-AR
FXMQ50-140PB
Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between GND and Vcc, Hw, Hv, or Hu
terminals of the motor connector (with five conductors).
White (1)
Orange (2)
Brown (3)
Blue (4)
— (5)
— (6)
Red (7)
FG
Vsp
Vcc
GND
—
—
Vdc
Measuring points
Judgment criteria
1-4
1
Ω
or more
2-4
1
Ω
or more
3-4
1
Ω
or more
7-4
1
Ω
or more
Gray (5)
Pink (4)
Orange (3)
Blue (2)
Yellow (1)
GND
Vcc
Hw
H
V
H
U
Connector signal wire use (X2A)