Troubleshooting by Error Code
SiME341909EA
202
Part 6 Service Diagnosis
Reference
CHECK 16
Refer to page 275.
Replace the relevant fan motor.
(
#
2)
YES
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost
balance or short circuit is
caused between U, V,
W phases.
Check for the connector
(power supply cable) of the
fan motor.
CHECK 16
Replace the fan PCB. (
#
1)
YES
The HAP
lamp on A3P, A6P
blinks, but that on A4P, A7P
does not blink.
#
3
RXQ6-12AR: A3P
RXQ14/16AR: A3P, A6P
Turn ON the power supply to check for the following LED lamps.
(1) HAP lamp on the inverter PCB (
#
3)
(2) HAP lamp on the fan PCB (
#
1)
Replace the fan motor. (
#
2)
NO
A
NO