![background image](http://html1.mh-extra.com/html/daikin/vrv-x-rxq10aryfk/vrv-x-rxq10aryfk_service-manual_2459229023.webp)
SiME341909EA
Specifications
Part 1 General Information
17
Model
RXQ14ARYFK
RXQ16ARYFK
Cooling capacity at T1
1
Capacity
kW
40.0
45.0
Capacity
Btu/h
136,500
153,550
EER
kW/kW
3.54
3.42
EER
Btu/h∙W
12.08
11.68
Pl
kW
11.3
13.2
Cooling capacity at T3
1
Capacity
kW
34.1
34.6
Capacity
Btu/h
116,400
118,000
EER
kW/kW
2.73
2.77
EER
Btu/h∙W
9.31
9.44
Pl
kW
12.5
12.5
Cooling capacity at T4
1
Capacity
kW
17.8
22.0
Capacity
Btu/h
60,900
75,000
EER
kW/kW
2.70
2.96
EER
Btu/h∙W
9.23
10.14
Pl
kW
6.6
7.4
Allowed Indoor capacity
index connection
Norn.
350
400
Min.
175
200
Max.
455
520
Dimensions
Height
mm
1,657
1,657
Width
mm
1,240
1,240
Depth
mm
765
765
Packing dimensions
Height
mm
1,830
1,830
Width
mm
1,290
1,290
Depth
mm
810
810
Weight
Unit
285
285
Packed unit
315
315
Heat exchanger
Type
Cross fin coil
Cross fin coil
Fan
Type
Propeller
Propeller
Discharge direction
Vertical
Vertical
Motor
Quantity
2
2
Model
Brushless DC
Brushless DC
Output/pcs
W
750
750
Compressor
Motor
Quantity
2
2
Model
Inverter
Inverter
Type
Hermetically sealed scroll type
Hermetically sealed scroll type
Refrigerant
Refrigerant name
R-410A
R-410A
Charge
kg
11.7
11.8
Piping
connections
Liquid
Type
Brazing connection
Brazing connection
Diameter (OD)
mm
12.7
12.7
Gas
Type
Brazing connection
Brazing connection
Diameter (OD)
mm
28.6
28.6
Safety devices
High pressure switch, Fan driver overload protector,
Overcurrent relay,
Inverter overload protector,
Over/under voltage protection PCB
High pressure switch, Fan driver overload protector,
Overcurrent relay,
Inverter overload protector,
Over/under voltage protection PCB
Standard accessories
Installation manual, Operation manual,
Connection pipes, Clamps
Installation manual, Operation manual,
Connection pipes, Clamps
Drawing No.
3D124543
3D124543
Notes:
1. The data are based on the conditions shown in the table below.
Condition
Indoor DB (°C)
Indoor WB (°C)
Outdoor DB (°C)
Main standard
Reference standard
T1
27.0
19.0
35.0
Saudi SASO 2874:2016
ISO 15042:2011
T3
29.0
19.0
46.0
UAE.S 5010-5:2016
ISO 15042:2011
T4
26.6
19.4
48.0
Kuwait 2019 (MEW R-6)
AHRI-1230
2. For detailed contents, see installation/operational manual.
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...