As there are various combinations of indoor and outdoor units, the sub codes of A0 - A3 are not
shown in this table.
CE - 02
Infrared floor sensor error
A disconnection of the temperature correction circuit
(thermistor) of the infrared floor sensor has been
detected.
Check if the connector is properly connected.
CE - 03
Infrared floor sensor error
A short-circuit of the temperature correction circuit
(thermistor) of the infrared floor sensor has been
detected.
Check if the pins of the connector are touching each
other, and if any foreign matter on the PCB is causing a
short-circuit.
CE - 04
Infrared floor sensor error
An abnormality other than the ones mentioned above has
been detected.
Check if the temperature nearby the sensor is too high,
and if there is any foreign matter that may cause noise.
U4 - 01
Indoor-Outdoor transmission error
Refer to the
U4
flowchart.
UA - 13
Refrigerant type error
The type of refrigerant used for the indoor unit is different
from that used for the outdoor unit.
UA - 15
Not applicable for self-cleaning decoration panel (when
the self-cleaning decoration panel is mounted)
An outdoor unit is not applicable for the self-cleaning
decoration panel is connected.
Error code
Troubleshooting
Description of error
Diagnosis
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...