SiME341909EA
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
99
Note(s)
1.4.19 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ-AR is attached with a closing member kit, set the Second Code No.
to
02
or
03
.
1.4.20 Setting of Static Pressure Selection
FXDQ-PD, FXDQ-ND
: Factory setting
1.4.21 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment
(11 (21)-7), or manually using external static pressure settings (13 (23)-6).
FXMQ-PB
: Factory setting
∗
1 FXMQ40PB cannot be set to 180 or 200 Pa.
∗
2 FXMQ50/63/80/100/125PB cannot be set to 30 Pa.
∗
3 FXMQ140PB cannot be set to 30 Pa and 150-200 Pa.
FXFSQ-AR, FXAQ-AR
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
4
01
Draft prevention (Upward)
02
Standard
03
Ceiling soiling prevention (Downward)
Model
No.
First Code
No.
Second
Code No.
Contents
13 (23)
5
01
Standard (10 Pa)
02
High static pressure (30 Pa)
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
6
01
30 Pa (
∗
2) (
∗
3)
02
50 Pa
03
60 Pa
04
70 Pa
05
80 Pa
06
90 Pa
07
100 Pa
08
110 Pa
09
120 Pa
10
130 Pa
11
140 Pa
12
150 Pa (
∗
3)
13
160 Pa (
∗
3)
14
180 Pa (
∗
1) (
∗
3)
15
200 Pa (
∗
1) (
∗
3)
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...