![background image](http://html1.mh-extra.com/html/daikin/vrv-x-rxq10aryfk/vrv-x-rxq10aryfk_service-manual_2459229095.webp)
SiME341909EA
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
89
Note(s)
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
∗
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote controller is
resetting when returning to the normal mode.
∗
5. BRC1H81 series only
15 (25)
2
Direct duct connection
Not equipped
Equipped
—
—
3
Drain pump and humidifier
interlock selection
Not interlocked
Interlocked
—
—
5
Individual ventilation setting
— (Normal)
Individual
—
—
1b
4
Display of error codes on the
remote controller
—
Two-digit display
—
Four-digit
display
14
Setting restricted/permitted of
airflow block
Refer to the page on the right for details.
1c
0
Room temperature display
Not displayed
Displayed
—
—
01
(
∗
5)
Thermostat sensor
Indoor unit
thermistor
Controller
thermistor
—
—
—
12
(
∗
5)
Window contact B1
Do not use
Use
—
—
—
13
(
∗
5)
Key card contact B2
Do not use
Use
—
—
—
1e
(
∗
5)
02
Setback function
No Setback
Heating only
Cooling only Heating and
Cooling
—
07
Rotation overlap time
30 minutes
15 minutes
10 minutes
5 minutes
—
1B
(
∗
5)
08
Daylight saving time
Disable
Automatic
changeover
Manual
changeover
Centralized
control
—
Mode
No.
(
∗
2
)
First
Code
No.
Description
Second Code No.
Page
Reference
01
02
03
04
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...