Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
123
When operation parameters return to normal range, the capacity priority is switched OFF,
enable to reduce airflow rate depending on night-time low noise operation is still required
(end time for low-night noise operation is not reached or external input night-time low
noise operation is still closed).
Mode 2-30:
Power consumption limitation level 1
. If the system needs to be running
under power consumption limitation conditions via the external control adaptor for outdoor
unit DTA104A61/62. This setting defines the level power consumption limitation that will be
applied for level 1. The level is according the table.
Default: 3 (70%)
Field setting:
Mode 2-31:
Power consumption limitation level 2
. If the system needs to be running
under power consumption limitation conditions via the external control adaptor for outdoor
unit DTA104A61/62. This setting defines the level power consumption limitation that will be
applied for level 2. The level is according the table.
Default: 1 (40%)
Field setting:
Mode 2-38:
Emergency operation “Master”
. To disable permanent compressor operation:
in case of single module or “Master” unit of a multi outdoor system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: inverter 1 compressor is disabled.
Set 2: inverter 2 compressor is disabled. Only to make in case of 16-20 HP. Note that
compressor 2 is left side located.
Set 3: all compressors in this master module are disabled permanent.
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low
noise operation start setting
Low noise mode
instructing Operation sound
set with external low noise
setting
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with night-time low noise operation start
setting. (Factory setting is 10:00 PM.)
Set with night-time low noise operation end
setting. (Factory setting is 8:00 AM.)
∗
Low noise
mode instructing
∗
Operation sound set with
external low noise setting
∗
Night-time
If capacity priority is set in
capacity priority setting, the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with night-time low
noise operation end setting
∗
Operation sound mode
set with night-time low
noise operation setting
set 2-30
current limit set (%)
1
60
2
65
3
70 (default)
4
75
5
80
6
85
7
90
8
95
set 2-31
current limit set (%)
1
40 (default)
2
50
3
55
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...