Field Settings for Indoor Unit
SiME341909EA
92
Part 5 Field Settings and Test Operation
When the unit is equipped with an infrared presence/floor sensor:
: Factory setting
∗
Refer to
Compensating the temperature around people
.
Note that the control is automatically switched to the one performed only by the suction air
thermistor for indoor unit when the Second code No. is
01
during the group control.
To use the remote controller thermistor during the group control, select the Second code No.
02
in First code No.
6
.
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
6
01
Remote controller thermistor control is not permitted during
group control
02
Remote controller thermistor control is permitted during group
control
Mode No.
Second Code No.
10 (20)
2
01
02
02
02
#
02
03
11 (21)
8
01
01
02
03
#
04
01
The thermistor to be used
Remote controller thermistor
—
—
—
—
Suction air thermistor
—
Infrared floor sensor
—
—
—
First Code No.
The infrared floor
sensor is not used
Priority given to
the suction air
temperature (
)
Only the remote
controller thermistor
is used
Priority given to the
floor temperature (
)
Only the suction air
thermistor is used
Standard setting
(Factory setting)
Mode
No.
First
Code No.
Second
Code No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...