Field Settings for Outdoor Unit
SiME341909EA
114
Part 5 Field Settings and Test Operation
Reference
2.5.3 Check for Descriptions of Errors/Retries
Follow the procedure described below. This procedure is different than indicated in previous
Monitor mode.
The error codes for forced stop outdoor or retry are item:
17, 18, 19: description of error (outdoor system stopped operation).
23, 24, 25: description of retry.
The tables on next pages show a full list of possible error codes displayed on the 3 digit 7
segment display of the outdoor unit. The error code contains an upper and lower digit. To
scroll between upper and lower error digit, use the
SET (BS2)
button when the select
number in the monitor mode is chosen:
No. 17-19 for error: System operation stopped.
No. 23-25 for retry: System attempts to keep operation.
The errors cover problems detected in the outdoor unit or the communication.
Errors detected on the indoor unit are not shown on the outdoor display. For inspecting error
code on indoor unit, please consult:
Display of the remote controller connected to the indoor units.
If there are no remote controllers, there should be a central control device set up. Prior to
start up, make the necessary group number settings on each indoor unit.
Error Codes and Descriptions
.
SEG1 SEG2 SEG3
Normal
Normal
: hold 5 seconds
: BLINKS
: ON
: OFF
Legend Segment
MODE
BS1
MODE
BS1
RETURN
BS3
RETURN
BS3
SET
BS2
SET
BS2
SET
BS2
To enter monitor mode, press the
MODE (BS1)
button while in
normal mode.
Press the
SET (BS2)
button to set
the 7 segment display to any of the
error or retry items listed in the table
below.
Selecting error/retry item
Displaying check 1
Displaying check 2
Press the
RETURN (BS3)
button.
Error (Retry) codes will appear on the
7 segment display.
Press the
SET (BS2)
button.
Detailed error (retry) codes will appear on
the 7 segment display.
Pressing the
MODE (BS1)
button will
return the mode to normal mode.
Press the
RETURN (BS3)
button to set
monitor mode to the initial state.
Press
SET (BS2)
button.
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...