6 Configuration
Installation and operation manual
18
8T7Y1B
VRV IV compressor unit for indoor installation
4P408443-1B – 2016.04
3
Connect the power supply as follows:
3N~ 50 Hz
380-415 V
L1 L2 L3
L1 L2 L3
N
X1M
a
b
c
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable
4
Route the wiring through the frame, and fix the cables (power
supply and transmission wiring) with cable ties.
INFORMATION
To make routing the wiring easier, you can turn the switch
box horizontally by loosening the screw on the left side of
the switch box.
1×
c
≥50 mm
a
b
b
X1M
L1
F1F2
L2 L3 N
c
a
c
X2M
A1P
b
a
X1M X2M
5 HP
≥50 mm
a
b
b
a
X1M
X1M
A1P
X1M
b
a
c
c
8 HP
X1M (A1P)
c
a
Transmission wiring
b
Power supply
c
Cable tie
5
Reattach the service covers.
6
Connect an earth leakage circuit breaker and fuse to the power
supply line.
5.8
Finishing the compressor unit
installation
5.8.1
To finish the transmission wiring
After installing the transmission wires inside the unit, wrap them
along with the on-site refrigerant pipes using finishing tape, as
shown in figure below.
a
b
c
d
e
a
Liquid pipe
b
Gas pipe
c
Insulator
d
Transmission wiring (F1/F2)
e
Finishing tape
6
Configuration
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
6.1
Making field settings
6.1.1
About making field settings
To configure the heat pump system, you must give input to the
compressor unit's main PCB (A1P). This involves the following field
setting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
▪ DIP switches (only change the factory settings if you install a cool/
heat selector switch).
Field settings are defined by their mode, setting and value. Example:
[2‑8]=4.
PC configurator
You can also make field settings through a personal computer
interface (for this, option EKPCCAB is required). The installer can
prepare the configuration (off-site) on PC and afterwards upload the
configuration to the system.
See also:
"6.1.9 To connect the PC configurator to the compressor
Mode 1 and 2
Mode
Description
Mode 1
(monitoring
settings)
Mode 1 can be used to monitor the current
situation of the compressor unit. Some field
setting contents can be monitored as well.
Summary of Contents for VRV IV RKXYQ8T7Y1B
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ...4P408443 1 B 0000000 4P408443 1B 2016 04 Copyright 2015 Daikin ...