5 Installation
Installation and operation manual
10
8T7Y1B
VRV IV compressor unit for indoor installation
4P408443-1B – 2016.04
Transmission wiring
Sh shielded cable (2
wires)
Vinyl cords
0.75~1.25 mm²
(using shielded cable for the
transmission wiring is mandatory
for 5 HP, and optional for 8 HP)
Maximum wiring length
(= distance between compressor
unit and furthest indoor unit)
300 m
Total wiring length
(= distance between compressor
unit and all indoor units, and
between compressor unit and
heat exchanger unit)
600 m
If the total transmission wiring exceeds these limits, it may
result in communication error.
5
Installation
5.1
Opening the units
5.1.1
To open the compressor unit
DANGER: RISK OF BURNING
DANGER: RISK OF ELECTROCUTION
1
Remove the service cover of the compressor unit.
5×
5×
5 HP
8 HP
2
If you want to make
field settings
, remove the inspection
cover.
5 HP
8 HP
3
If you want to connect
electrical wiring
, remove the switch box
cover.
4×
4×
5 HP
8 HP
5.2
Mounting the compressor unit
5.2.1
Guidelines when installing the
compressor unit
Check the strength and level of the installation ground so that the
unit will not cause any operating vibration or noise. If the vibration
might be transmitted to the building, use a vibration-proof rubber
(field supply).
You can install the compressor unit directly on the floor or on a
structure.
▪
On the floor.
You do NOT have to fix the unit with anchor bolts.
▪
On a structure.
Fix the unit securely with anchor bolts, nuts and
washers (field supply) to the structure. The foundation (steel beam
frame or concrete) must be larger than the grey marked area.
a
≤
480
516
≥666
426 (5 HP)
600 (8 HP)
≥640 (5 HP)
≥800 (8 HP)
(mm)
Minimum foundation
a
Anchor point (4×)
INFORMATION
The recommended height of the upper protruding part of
the bolts is 20 mm.
20 mm
5.3
Connecting the refrigerant piping
DANGER: RISK OF BURNING
5.3.1
Using the stop valve and service port
To handle the stop valve
▪ Make sure to keep all stop valves open during operation.
▪ The stop valve is factory closed.