background image

English

14

11-2-1 Procedure of Adding Refrigerant charging
1.

Make sure the following works are complete in accordance with 
the installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Installation work for BS, indoor unit

2.

Calculate the “additional charging amount” using “How to calcu-
late the additional refrigerant to be charged” in “

6-5 Example of 

connection

”.

3.

Open the valve B (

See the figure 30

. The valve A,C and the liquid 

pipe, suction gas pipe, HP/LP gas pipe shutoff valves must be left 
closed), and charge the refrigerant of the “additional charging 
amount” from the liquid side shutout valve service port.

(Refer to figure 30)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

Refrigerant charge port

5.

HP/LP gas pipe shutoff valve

6.

Suction gas shutoff valve

7.

Liquid pipe shutoff valve

8.

Valve A

9.

Valve B

10.

Valve C

11.

Outdoor unit

12.

To BS, indoor unit

13.

Field pipings

14.

Refrigerant flow

15.

Shutoff valve

16.

Service port

4.

If the “additional charging amount” was charged fully, close the 
valve B and go to step 6.
If the “additional charging amount” was not charged fully, close 
the valve B and go to step 5.

5.

Perform the refrigerant charging following [Automatic refrigerant 
charging operation procedure] as shown below. And charge the 
remaining refrigerant of the “additional charging amount”.

Note

For performing the automatic refrigerant charging operation, the 
push button on the PC-bord (A1) of outdoor unit are used. (See 
figure 29.)
And the refrigerant are charged from the refrigerant charge port 
via the valve A. (See figure 31.) For operating the push button and 
opening or closeing the valves, follow the procedure.

During Automatic refrigerant charging operation, the system will 
select charging mode (cooling mode or heating mode) by the tem-
perature condition as follows.

When cahrging in cooling mode, the system will stop operation 
when the required amount of refrigerant is charged.
During charging in heating mode, a person must manually close 
valve A and stop operation.
Beforehand, check the remaining refrigerant that is needed to 
charge based on the “additional charging amount” in step 2 and 
the charged amount in step 3.

The refrigerant will be charged about 30kg in one  hour at outdoor 
temp. 30°C DB (about 12kg at outdoor temp. 0°C DB).

During Automatic refrigerant charging operation, you can stop the 
operation forcedly by pushing MODE button (BS1).

(Refer to figure 31)

1.

Meauring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

Refrigerant charge port

5.

HP/LP gas pipe shutoff valve

6.

Suction gas pipe shutoff valve

7.

Liquid pipe shutoff valve

8.

Valve A

9.

Valve B

10.

Valve C

11.

Outdoor unit

12.

To BS, indoor unit

13.

Field pipings

14.

Refrigerant flow when charging

15.

Shutoff valve

16.

Service port

[Automatic refirgerant charging operation procedure]

Note

The marks of LED mean as follows.

h

 : OFF

i

 : ON

j

 : Blinking

 : OFF, ON or Brinking

(1) Open the liquid pipe, suction gas pipe and HP/LP gas pipe shutoff 

valves. (The valve A~C must be closed. See figure 31.)

(2) • Close the EL. COMPO. BOX (1) lid and all front panel except on 

the EL. COMPO. BOX (1) side. (*1) And turn the power to the 
outdoor unit and all connected BS, indoor units. (*2)

• After H2P stop blinking (about 12 minutes after turning on the 

power), check H2P is OFF.
If H2P is ON, check the malfunction code in the remote control-
ler of indoor unit and correct the malfunction in accordance with 
[Remote controller display malfunction code] in chapter 11-2-2.

(3) Check the LED. And push the MODE button (BS1) once if the LED 

displays is not as below.

(4) Push the TEST button (BS4) once. (The LED displays will change 

as below.)

(5) Hold the TEST button (BS4) down for 5 seconds or more.

(The LED displays will change as below and fan of outdoor unit 
will start rotation.)

(6) When the compressor start working and the LED displays change 

any state in below (*3), go to “In case of cooling mode” or “In case 
of heating mode” in accordance with the LED displays.

In case of cooling mode

(7) Push the TEST button (BS4) once within 5 minutes after proce-

dure (5) (*4) and close the all front panels (*5).
After that, open the valve A immediately (See figure 31) (*6) and 
watch the remote controller display of indoor unit.

(8) If the remote controller display shows “PE” code (*7), ready to 

close the valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve 
A immediately and refer to [Remote controller cooling mode mal-
function code]

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(9) When the compressor stop working (the fan may continue rota-

tion.), close the valve A immediately (*8).
And check the LED displays are as below and the remote control-
ler display shows “P9” code.

After checking, push the MODE button (BS1) once and the charg-
ing is complete.

In case of heating mode

(7) Push the TEST button (BS4) once within 5 minutes after proce-

dure (5) (*4) and close the all front panels.
After that, open the valve A immediately (See figure 31) (*6) and 
check the charged amount by meauring device.
During operation, if the remote controller display shows “P2” or 
“P8” code, close the valve A immediately and refer to [Remote 
controller heating mode malfunction code].

Outdoor temp. : 0˚C DB ~  43˚C DB
Indoor temp. :

10˚C DB ~  32˚C DB

Less than above range

Cooling mode

Heating mode

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

H1P H2P H3P H4P H5P H6P H7P

i i i i i i i

H1P H2P H3P H4P H5P H6P H7P

h

j

h

h

h

H1P H2P H3P H4P H5P H6P H7P

j j j

h

i

h

i

Go to “In case of 
cooling mode”

j j

h

h

i

h

i

Go to “In case of 
heating mode”

H1P H2P H3P H4P H5P H6P H7P

i j j i i i i

01_EN_3P201178-4B.fm  Page 14  Friday, May 18, 2007  7:58 PM

Summary of Contents for VRV III REYQ8PY1B

Page 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Page 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Page 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Page 6: ...3P201178 4B EM07A013 0705 HT...

Page 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Page 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Page 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Page 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Page 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Page 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Page 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Page 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Page 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Page 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Page 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Page 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Page 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Page 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Page 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Page 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Page 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Page 24: ...English 18 NOTES...

Reviews: