background image

15

English

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(8) When the required amount of refrigerant is charged, close the 

valve A (See figure 31) (*8) and push the RETURN button (BS3) 
once. And then go to procedure (9).

(9) Push the MODE button (BS1) once, and the charging is complete.

Notes (*1)~(*9)

(*1) Lead the refrigerant charge hose etc from the pipe intake. 

All front panels must be closed at the procedure (7).

(*2) • If you perform the refrigerant charging operation within the 

refrigerant system that have the power off unit, the operation 
cannot finish properly.
Check the number of outdoor and indoor units that is powered.
For checking, see [How to check how many units are con-
nected] in chapter 11-1.

• To energize the crankcase heater, make sure to turn on for 

6 hours before starting operation.

(*3) It takes about 2~10 minutes for getting stability of refrigerant state.

If the additional refrigerant is little and operation is started before 
getting stability, the system can not judge the charging amount 
precisely and it cause over charge.

(*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2” code 

will displayed in the remote controller. In this case, refer [Remote 
controller cooling (or heating) mode malfunction code].

(*5) If the front panel is opened during the operation, the system can-

not operate properly.

(*6) If you leave the system without connecting the refrigerant tank or 

opening the valve A for 30 minutes or more, the system stop oper-
ation and “P2” code are displayed in remote controller.
In this case, refer [Remote controller cooling (or heating) mode 
malfunction code].

(*7) Depending on the situation of operation such as the charging 

amount is little, the “PE” code may not be displayed and the “P9” 
code may be displayed.

(*8) Always close the valve A and take the tank off.

The refrigerant charge port of this unit have electric expansion 
valve and the valve are closed when charging is finished. However, 
the valve will opened when ather operation (Check operation, 
nomal operation, etc.). If you leave the tank connected, the refrig-
erant will charged and it cause over charge.

[Remote controller cooling mode malfunction code]

[Remote controller heating mode malfunction code]

6.

After completing the additional refrigerant charging, record the 
charging amount on the accessory “REQUEST FOR THE INDI-
CATON” label (Installation records) and adhere it to the back side 
of the front panel. Also, record the factory charged refrigerant 
amount, additional refrigerant amount in the field and total refrig-
erant amount of the system to “ADDITIONAL REF. CHARGE” 
label and adhere in the proximity of the refrigerant charge port.
About “ADDITIONAL REF. CHARGE” label, refer to [Important 
information regarding the refrigerant used] in “

1-2 Special notice 

of product

”.

11-2-2 Procedure of check operation

Check operation perform the following work. Do the check opera-
tion following below.
Otherwise, malfunction code “U3” will be displayed in the remote 
controller and nomal operation can not be carried out.

„

Check of shutoff valve opening

„

Check of miswiring

„

Judgment of piping length

„

Check of refrigerant overcharge

Note

Check operation can not carried out at outdoor temp. less than –5°C.
Perform the check operation at day or time that outdoor temp. is –5°C 
or more.

[Check Operation Procedure]

(1) Close the EL. COMPO. BOX (1) lid and all front panels except as 

the side of the EL. COMPO. BOX (1) and turn on the power to the 
outdoor unit and all connected BS, indoor units. (Be sure to turn 
the power on at least 6 hours before operation in order to have 
power running to the crank case heater.)

(2) Make the onsite settings as needed using the push button (BS1-

BS5) on the outdoor unit PC-board (A1P) with the power on. (See 

12. ONSITE SETTINGS

”)

(3) Perform the check operation following the Check Operation Method of 

the [Service Precautions] label (lower) on the EL. COMPO. BOX (1) 
lid (see figure 32). The system operation for about 40~60 minutes and 
automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after 
the system stop, check operation is completed. Normal operation will 
be possible after 5 minutes. If the malfunction code is displayed in the 
remote controller, correct the malfunction following [Remote controller 
displays malfunction code] and perform the check operation again.

(Refer to figure 32)

1.

EL. COMPO.BOX (1) lid

2.

EL. COMPO.BOX (2) lid

3.

[Service Precaution] label (upper)

4.

[Service Precaution] label (lower)

Note

For interrupting the check operation, push RETURN button (BS3).

Code

The work contents

PE

Charging is almost finished. Ready to close the valve A.

PA

PH

The refrigerant tank is empty. Close the valve A and 
replace empty tank to the new tank. After changing the 
tank, open the valve A again.

Beware the fan running. The outdoor unit does not 
stop operation.

P8

Close the valve A immediately, and restart the operation 
from procedure (3).

P2

Operation is interrupted. Close the 
valve A immedeately and check the 
below items.

Check if HP/LP gas pipe, suc-
tion gas pipe or liquid pipe 
shutoff valve is opened.

Check the refrigerant tank is 
connected and the valve A 
was opend.

Check if the air inlet and outlet 
of the indoor unit are not 
closed by an obstruction.

After correcting the 
abnormality, restart 
the operation from 
procedure (3).

Operation is stoped abnormally. 
Close the valve A immediately. Con-
firm the malfunction code and cor-
rect the abnormality following the 
[Remote controller displays mal-
function code] in chapter 11-2-2.

P9

Charging is finished. Close the valve A and take the refrig-
erant tank off.

Code

The work contents

P8

Close the valve A immediately and push the TEST button 
(BS4) once. And restart from procedure (7) of “In case of 
heating mode”.

P2

Operation is interrupted. Close the valve A immedeately 
and check the below items.

Check if HP/LP gas pipe, suction gas pipe or liquid 
pipe shutoff valve is opened.

Check the refrigerant tank is connected and the valve 
A was opend.

Check if the air inlet and outlet of the indoor unit are 
not closed by an obstruction.

01_EN_3P201178-4B.fm  Page 15  Friday, May 18, 2007  7:58 PM

Summary of Contents for VRV III REYQ8PY1B

Page 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Page 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Page 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Page 6: ...3P201178 4B EM07A013 0705 HT...

Page 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Page 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Page 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Page 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Page 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Page 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Page 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Page 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Page 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Page 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Page 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Page 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Page 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Page 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Page 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Page 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Page 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Page 24: ...English 18 NOTES...

Reviews: