background image

11

English

7.

When routing out the transmission wiring from the 
knockout hole.

8.

When routing out the power/ground wires from the right side.

9.

Power wiring

10.

Ground wire

11.

Transmission wiring

12.

When wiring, exercise sufficient caution not to detach the 
acoustic insulators from the compressor.

13.

Secure to the back side of the support beam using the 
accessory clamp (1).

14.

Retain to the back of the column support with the acces-
sory clamp (2).

Note

After wiring work is completed, check to make sure there are no loose 
connections among the electrical parts in the EL.COMPO.BOX (1) 
(right).

8.

AIR TIGHT TEST AND VACUUM DRYING

 After finished piping work, carry out air tight test and vacuum drying.

Note

Always use nitrogen gas for the airtightness test.

Absolutely do not open the shutoff valve until the main power ciruit 
insulation measurement has been completed. (measuring after 
the shutoff valve is opened will cause the insulation value to drop.)

<Needed tools>

<The system for air tight test and vacuum drying>

Referring to figure 25, connect an nitrogen tank, refrigerant tank, 
and a vacuum pump to the outdoor unit.
The refrigerant tank and the charge hose connection to refrigerant 
charge port or the valve A in figure 25 are needed in “

11. ADDI-

TIONAL REFRIGERANT CHARGE AND CHECK OPERATION

”.

(Refer to figure 25)

1.

Gauge manifold

2.

Nitrogen

3.

Measuring device

4.

R410A tank (with siphon)

5.

Vacuum pump

6.

Charge hose

7.

Refrigerant charge port

8.

HP/LP gas pipe shutoff valve

9.

Suction gas pipe shutoff valve

10.

Liquid pipe shutoff valve

11.

Valve A

12.

Valve B

13.

Valve C

14.

Outdoor unit

15.

To BS (or indoor) unit

16.

Shutoff valve

17.

Service port

18.

Field piping

19.

Gas flow

Note

The airtightness test and vacuum drying 
should be done using the service ports of 
HP/LP gas pipe, suction gas pipe and liquid 
pipe shutoff valve.
See the [R410A] Label attached to the front 
plate of the outdoor unit for details on the 
location of the service port (see figure at right)

See 

[Shutoff valve operation procedure] 

in 

11-1 Before working

” for details on han-

dling the shutoff valve.

The refrigerant charge port is connected to unit pipe.
When shipped, the unit contains the refrigerant, so use caution 
when attaching the charge hose.

<Air tight test>

Pressurize the liquid pipe, suction gas pipe and HP/LP gas pipe from 
the service ports of each shutoff valve to 4.0MPa (40bar) (do not 
pressurize more than 4.0MPa (40bar)). If the pressure does not drop 
within 24 hours, the system passes the test.
If there is a pressure drop, check for leaks, make repairs and perform 
the airtight test again.

<Vacuum drying>

Evacuate the system from the liquid pipe, suction gas pipe and 
HP/LP gas pipe shutoff valve service ports by using a vacuum 
pump for more than 2 hours and bring the system to –100.7kPa or 
less. After keeping the system under that condition for more than 1 
hour, check if the vacuum gauge rises or not. If it rises, the system 
may either contain moisture inside or have leaks.

Note

If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work 
takes long enough that condensation may form on the inside of 
the pipes, if rain might enter the pipes during work, etc.)

(1) After performing the vacuum drying for two hours, pressurize to 

0.05 MPa (i.e., vacuum breakdown) with nitrogen gas, then 
depressurize down to –100.7 kPa for an hour using the vacuum 
pump (vacuum drying). 

(2) If the pressure does not reach –100.7 kPa even after depressur-

izing for at least two hours, repeat the vacuum breakdown - vac-
uum drying process.

After vacuum drying, maintain the vacuum for an hour and make sure 
the pressure does not rise by monitoring with a vacuum gauge.

9.

PIPE INSULATION

Insulation of pipes should be done after performing “

8. AIR TIGHT 

TEST AND VACUUM DRYING

”.

Always insulate the liquid piping, the HP/LP gas piping, the suc-
tion gas piping, the gas piping and these pipe connections.
Failing to insulate the pipes may cause leaking or burns.
Especially, be sure to insulate the HP/LP gas piping as withstand-
ing as the suction pipe because the suction gas follows in the 
HP/LP gas piping when the system is whole cooling mode.
And be sure to use the insulation which can withstand such tem-
peratures of 120°C or more for the HP/LP gas piping and the gas 
piping because the high pressure gas follows in these pipings.

Reinforce the insulation on the refrigerant piping according to the 
installation environment. Condensation might form on the surface 
of the insulation. Refer to the below.

„

Ambient temperature : 30°C, humidity : 75% to 80% RH : min. 
thickness : 15mm.

„

If the ambient temperature exceeds 30°C and the humidity 
80% RH, then the min. thickness is 20mm.
See the Engineering data book for detail.

If there is a possibility that condensation on the shutoff valve 
might drip down into the indoor unit through gaps in the insulation 
and piping because the outdoor unit is located higher than the 
indoor unit, etc., this must be prevented by caulking the connec-
tions, etc. 

(Refer to figure 26)

The piping lead-out hole lid should be attached after opening a 
knock hole. 

(Refer to figure 27)

If small animals and the like might enter the unit through the pip-
ing lead-out hole, close the hole with blocking material (procured 
on site) after completion of “

11. ADDITIONAL REFRIGERANT 

CHARGE AND CHECK OPERATION

”. 

(Refer to figure 30)

(Refer to figure 26)

1.

Insulation material

2.

Caulking, etc.

(Refer to figure 27)

1.

Piping lead-out hole lid

2.

Open a knock hole at “

”. 

3.

Block  “

”.

Note

After knocking out the holes, we recommend you remove burrs in 
the knock holes (

See figure 27

) and paint the edges and areas 

around the edges using the repair paint.

Gauge manifold
Charge hose 
valve

• To prevent entry of any impurities and insure 

sufficient pressure resistance, always use the 
special tools dedicated for R410A.

• Use charge hose that have pushing stick for 

connecting to service port of shutoff valves or 
refrigerant charge port.

Vacuum pump

• The vacuum pump for vacuum drying should 

be able to lower the pressure to –100.7kPa 
(5 Torr –755mm Hg).

• Take care the pump oil never flow backward 

into the refrigerant pipe during the pump stops.

[R410A] Label

01_EN_3P201178-4B.fm  Page 11  Friday, May 18, 2007  7:58 PM

Summary of Contents for VRV III REYQ8PY1B

Page 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Page 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Page 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Page 6: ...3P201178 4B EM07A013 0705 HT...

Page 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Page 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Page 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Page 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Page 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Page 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Page 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Page 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Page 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Page 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Page 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Page 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Page 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Page 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Page 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Page 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Page 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Page 24: ...English 18 NOTES...

Reviews: