6-3 Pipe connection

Be sure to perform nitrogen permutation or nitrogen blow when 
brazing. 

(Refer to figure 8)

Brazing without performing nitrogen permutation or nitrogen 
blow into the piping will create large quantities of oxidized film on 
the inside of the pipes, adversely affecting valves and compres-
sors in the refrigerating system and preventing normal operation.

(Refer to figure 8)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Nitrogen

4.

Taping

5.

Handy valve

6.

Regulator

The pressure regulator for the nitrogen released when doing 
the brazing should be set to about 0.02 MPa (0.2kg/cm

Enough to feel a slight breeze on your cheek).

Note

Do not use anti-oxidants when brazing the pipe joints.
Residue can clog pipes and break equipment.

6-4 Connecting the refrigerant piping
1.

Direction to bring out the pipes
The local interunit piping can be connected either forward or to 
the sides (taken out through the bottom) as shown in the figure 10. 
When passing out through the bottom, use the knock hole in the 
bottom frame.

(Refer to figure 10)

1.

Left-side connection

2.

Front connection

3.

Right-side connection

Precautions when knocking out knock holes

Open knock hole in the base frame by drilling the 4 concave 
around it with a 6mm bit. 

(Refer to figure 11)

(Refer to figure 11)

1.

Knock hole

2.

Drill

3.

Concave section (4 points)

Be sure to avoid damaging the casing

After knocking out the holes, we recommend you remove any 
burrs and paint them using the repair paint to prevent rusting.

When passing electrical wiring through the knock holes, protect the wir-
ing with a conduit or bushings, making sure not to damage the wiring.

2.

Removing Pinch Piping

When connecting refrigerant piping to an outdoor unit, remove 
the pinch piping using the procedure in the figure 12.

(Refer to figure 12)

About handling of shutoff valves, refer to [Shutoff valve opera-
tion procedure] in “

11-1 Before working

”.

Caution

After removing the gass, remove the pinch piping.
Any gas remaining inside may blow off the pinch piping when you dis-
solve the brazing, causing damage.

(Refer to figure 12)

1.

Pich piping (4 pieces)

2.

Do not remove the relay piping.

3.

Pinch piping

4.

Procedure 1 : Confirm the shutoff valve is closed.

5.

Procedure 2 : Connect a charge hose to the service port 
of shutoff valve and remove the gas in the pinch piping.

6.

Procedure 3 : After removing the gas in the pinch piping, 
dissolve the brazing using a burner and remove the 
pinch piping.

3.

Connecting refrigerant piping to outdoor units

Figure 13 shows the example of connecting refrigerant piping to 
outdoor units.

The local interunit piping next accesorry pipes are field supplyed.

(Refer to figure 13)

1.

When connected to the front

2.

When connected at lateral side (bottom)

3.

Remove the shutoff valve cover to connect.

4.

Remove the knock hole on the bottom frame and route 
the piping under the bottom frame.

5.

Liquid pipe shutoff valve

6.

Suction gas pipe shutoff valve

7.

HP/LP gas pipe shutoff valve

8.

Brazing

9.

Liquid side accessory pipe (1)

10.

Suction gas side accessory pipe (1)

11.

HP/LP gas side accessory pipe (1)

12.

L type accessory joint (1)

13.

L type accessory joint (2)

14.

Liquid side accessory pipe (2)

15.

Suction gas side accessory pipe (2)

16.

HP/LP gas side accessory pipe (2)

17.

In case of Q8 type use the Accessory joint for connecting 
the Suction gas side accessory pipe (2) to Suction gas 
side shutoff valve.

18.

Accessory joint

Note

Make sure the onsite piping does not come into contact with other 
piping or the bottom frame or side panels of the unit.

4.

Branching the refrigerant piping
Heed the restrictions below when installing the refrigerant branch-
ing kit and read the installation instruction manual with the kit.
(Improper installation could lead to malfunctioning or breakdown 
of the outdoor unit.)

<REFNET joint>

Install the REFNET joint so it splits horizontally or vertically.

(Refer to figure 14)

1.

Horizontal

2.

A-arrow view

3.

Horizontal surface

4.

±30° or less

5.

Vertical

<REFNET header>

Install the REFNET header so it splits horizontally.

(Refer to figure 15)

1.

Horizontal surface

2.

B-arrow view

01_EN_3P201178-4B.fm  Page 5  Friday, May 18, 2007  7:58 PM

Summary of Contents for VRV III REYQ8PY1B

Page 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Page 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Page 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Page 6: ...3P201178 4B EM07A013 0705 HT...

Page 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Page 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Page 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Page 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Page 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Page 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Page 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Page 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Page 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Page 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Page 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Page 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Page 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Page 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Page 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Page 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Page 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Page 24: ...English 18 NOTES...

Reviews: