background image

English

12

10. CHECKING OF DEVICE AND INSTAL-

LATION CONDITIONS

Be sure to check the followings.

For those doing electrical work

1.

Make sure there is no faulty transmission wiring or loosing of a nut.
See “

7-4 Transmission Wiring Connection Procedure

”.

2.

Make sure there is no faulty power wiring or loosing of a nut.
See “

7-5 Power Wiring Connection Procedure

”.

3.

Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

For those doing pipe work

1.

Make sure piping size is correct. 
See “

6-1 Selection of piping material and Refrigerant branch-

ing kit

”.

2.

Make sure insulation work is done. 
See “

9. PIPE INSULATION

”.

3.

Make sure there is no faulty refrigerant piping.
See “

6. REFRIGERANT PIPING

”.

11. ADDITIONAL REFRIGERANT 

CHARGE AND CHECK OPERATION

The outdoor unit is charged with refrigerant when shipped from the factory, 
but depending on the size and length of the piping when installed, it may 
require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter.
And then carry out the check operation.

11-1 Before working

[About the refrigerant tank]

Check whether the tank has a siphon pipe before charging and place 
the tank so that the refrigerant is charged in liquid form.
(See the figure below.)

Note

Always use the proper refrigerant (R410A). If charged with the 
refrigerant containing an improper material, it may cause an 
explosion or accident.

R410A is a mixed refrigerant, so charging it as a gas will cause 
the refrigerant composition to change, which may prevent normal 
operation.

[Shutoff valve operation procedure]

When operating the shutoff valve, follow the procedure instructed below.

Note

Do not open the shutoff valve until “

10. CHECKING OF DEVICE 

AND INSTALLATION CONDITIONS

” are completed. If the shutoff 

valve is left open without turning on the power, it may cause refrig-
erant to buildup in the compressor, leading insulation degradation.

Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it 
might break the valve body.

When using a service port, use the charge hose.

After tightening the cap, make sure no refrigerant gas is leaking.

Tightening torque

The sizes of the shutoff valves on each model and the tightening 
torque for each size are listed in the table below.

<Size of Shutoff Valve>

(Refer to figure 28)

1.

Service port

2.

Cap

3.

Hex holes

4.

Shaft (valve body)

5.

Seal section 

To open

1.

Remove the cap and turn the shaft counterclockwise with the 
hexagon wrench (JISB4648).

2.

Turn it until the shaft stops.

3.

Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)

To close

1.

Remove the cap and turn the shaft clockwise with the hexagon 
wrench (JISB4648).

2.

Securely tighten the valve until the shaft contacts the main body seal.

3.

Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)

<Tightening torque>

With siphon pipe

Other tanks

Stand the tank upright and charge.
(The siphon pipe goes all the way inside, 
so the tank does not need be put 
upside-down charge in liquid form.)

Stand the tank upside-down and charge.

8HP type 10HP type 12HP type 14HP type 16HP type

Liquid pipe 
shutoff valve

φ

9.5

φ

12.7

The 12HP type corresponds to 
the 12.7-diameter onsite pip-
ing using the accessory pipe.

Suction gas 
shutoff valve

φ

25.4

The 8HP type corresponds to the 19.1-diameter 
onsite piping using the accessory pipe.
The 10HP type corresponds to the 22.2-diameter 
onsite piping using the accessory pipe.
The 12-16 HP type corresponds to the 28.6-diam-
eter onsite piping using the accessory pipe.

HP/LP gas 
shutoff valve

φ

19.1

The 8HP type corresponds to the 15.9-diameter 
onsite piping using the accessory pipe.
The 14 · 16 HP type corresponds to the 22.2-diam-
eter onsite piping using the accessory pipe.

Shutoff 
valve size

Tightening torque N·m (Turn clockwise to close)

Shaft (valve body)

Cap (valve lid) Service port

φ 

9.5

5.4 - 6.6

Hexagonal 

wrench

4 mm

13.5 - 16.5

11.5 - 13.9

φ 

12.7

8.1 - 9.9

18.0 - 22.0

φ 

19.1

27.0 - 33.0

Hexagonal 

wrench

8 mm

22.5 - 27.5

φ 

25.4

01_EN_3P201178-4B.fm  Page 12  Friday, May 18, 2007  7:58 PM

Summary of Contents for VRV III REYQ8PY1B

Page 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Page 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Page 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Page 6: ...3P201178 4B EM07A013 0705 HT...

Page 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Page 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Page 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Page 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Page 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Page 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Page 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Page 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Page 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Page 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Page 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Page 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Page 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Page 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Page 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Page 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Page 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Page 24: ...English 18 NOTES...

Reviews: