English

2

The indoor and BS unit should be installed as far away from fluo-
rescent lighting as possible.
Remote controller (wireless kit) transmitting distance can result 
shorter than expected in rooms with electronic fluorescent lamps 
(inverter or rapid start types).

Do not install the air conditioner in the following locations:
(a) where a mineral oil mist or an oil spray or vapor is produced, 

for example in a kitchen.
Plastic parts may deteriorate and fall off or result in water leakage.

(b) where corrosive gas, such as sulfurous acid gas, is produced.

Corroding copper pipes or soldered parts may result in refrig-
erant leakage.

(c) near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the con-
trol system and result in a malfunction of the unit.

(d) where flammable gas may leak, where there are carbon fiber 

or ignitable dust suspensions in the air, or where volatile flam-
mables such as thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.

(e) Locations where small animals might build nests inside the unit.

If small animals enter and come in contact with electrical parts, 
this can cause malfunctions, smoke, and fire.

1-2 Special notice of product

[CLASSIFICATION]

This air conditioner comes under the term “appliances not accessible 
to the general public”.

[EMC CHARACTERISTICS]

VRV

III

 System is a class A product. In a domestic environment this 

product may cause radio interference in which case the user may be 
required to take adequate measures.

[REFRIGERANT]
 VRV

III

 System use R410A refrigerant.

The refrigerant R410A requires strict cautions for keeping the sys-
tem clean, dry and tight.
Read the chapter “REFRIGERANT PIPING” carefully and follow 
these procedures correctly.
A.Clean and dry

Foreign materials (including mineral oils such as SUNISO oil or 
moisture) should be prevented from getting mixed into the system.

B.Tight

Take care to keep the system tight when installing.
R410A does not contain any chlorine, does not destroy the 
ozone layer, and does not reduce the earth’s protection against 
harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is 
released.

Since R410A is a mixed refrigerant, the required additional refrig-
erant must be charged in its liquid state. If the refrigerant is 
charged in a state of gas, its composition changes and the system 
will not work properly.

Limit by the total maximum refrigerant charge

The total maximum refrigerant charge of a VRV

III

 system must be 

below 100kg, this to be in accordance with CE requirement 
(EN60335-2-40 standard).
This means that in case the total maximum refrigerant charge of the 
system (factory and additional charge) is equal to or more than 
100kg you must divide your multiple outdoor system into smaller 
independent systems, each containing less than 100kg refrigerant 
charge.
For factory charge, refer to the unit name plate.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the 
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type : R410A

GWP 

(1)

 value :      1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,

Q

 

the factory refrigerant charge of the product,

Q

 

the additional refrigerant amount charged in the field and

Q

 

+

the total refrigerant charge on the refrigerant charge label

    supplied with the product.
     The filled out label must be adhered in the proximity of the product
    charging port (e.g. onto the inside of the service cover).

(2)

 In case of multiple outdoor systems, only 1 label must be adhered, 

mentioning the total factory refrigerant charge of all outdoor units 
connected on the refrigerant system.

[DESIGN PRESSURE]

Since design pressure is 4.0MPa or 40bar (for R407C units : 3.3MPa 
or 33bar), the wall thickness of pipes should be more carefully selected 
in accordance with the relevant local and national regulations.

1-3 Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and eventual 
other parts, should be done in accordance with the relevant local and 
national regulations.

2.

INTRODUCTION

REYQ-P series are designed for outdoor installation and used for 
cooling and heating aplications. The REYQ8-16P system is exclu-
sive unit for single outdoor unit system. The unit can not use for 
independent unit of multi outdoor unit system. 
With this system, rated cooling capacity from 22.4kW to 45.0kW 
and rated heating capacity from 25.0kW to 50.0kW can be 
achieved.

The BS units that combined with REYQ-P system for changing 
the refrigerant flow to indoor units are BSVQ100, 160, 250P type 
only. To combine with other type BS unit will cause malfunction.

The indoor units that combined with REYQ-P system for air con-
ditioning are Daikin VRV series indoor units that compatible with 
R410A. To learn which indoor units are compatible with R410A, 
refer to the product catalogs. To combine with other refrigerant 
indoor unit will cause malfunction.

2-1 Combination

The indoor units can be installed in the following range.

Outdoor unit

Total capacity of indoor units

REYQ8PY1B .......................................100

~  260

REYQ10PY1B .....................................125

~  325

REYQ12PY1B .....................................150

~  390

REYQ14PY1B .....................................175

~  455

REYQ16PY1B .....................................200

~  520

If the total capacity of the connected indoor units exceeds the 
capacity of the outdoor unit, cooling and heating performance 
may drop when running the indoor units. See the capacity table in 
the Engineering Data Book for details.

3

5

6

2

1

4

1 factory refrigerant charge 

of the product : see unit 
name plate

 (2)

2 additional refrigerant 

amount charged in the field

3 total refrigerant charge

4 Contains fluorinated 

greenhouse gases covered 
by the Kyoto Protocol

5 outdoor unit

6 refrigerant cylinder and 

manifold for charging

01_EN_3P201178-4B.fm  Page 2  Friday, May 18, 2007  7:58 PM

Summary of Contents for VRV III REYQ8PY1B

Page 1: ...ir conditioner Installationsanleitung VRVIII System Klimaanlage Manuel d installation Conditionneur d air VRVIII System Manual de instalaci n Sistema de acondicionador de aire VRVIII Manuale di instal...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...nit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 300 Pattern 3 2 1 figure 6 1 2 1 2 3 figure 7 1300 1162 1 4 3 2 765 729 631 765 1 2 3 fig...

Page 4: ...OOUT DUNIT F1 F2 F1 F2 1 2 3 4 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 6 7 5 F1 F2 F1 F2 8 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 figur...

Page 5: ...9 10 13 14 15 11 12 18 19 16 17 1 2 1 3 2 figure 25 1 2 3 10 11 12 4 5 6 7 8 9 13 14 15 16 3 11 12 10 4 5 6 7 9 8 13 14 15 16 1 2 figure 29 figure 30 1 2 3 4 figure 32 1 2 3 4 5 figure 28 figure 24 3...

Page 6: ...3P201178 4B EM07A013 0705 HT...

Page 7: ...ge Excessive refrigerant in a closed ambient can lead to oxygen defi ciency Contact your dealer for more information Be sure to use only the specified accessories and parts for instal lation work Fail...

Page 8: ...ur multiple outdoor system into smaller independent systems each containing less than 100kg refrigerant charge For factory charge refer to the unit name plate Important information regarding the refri...

Page 9: ...igerant piping when installing the units If the work conditions in figure 2 do not apply contact your dealer or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space...

Page 10: ...rooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running For anti corrosion type use nuts with resin washers If the paint on nut connections comes off...

Page 11: ...ass remove the pinch piping Any gas remaining inside may blow off the pinch piping when you dis solve the brazing causing damage Refer to figure 12 1 Pich piping 4 pieces 2 Do not remove the relay pip...

Page 12: ...pipe length between outdoor unit 2 and indoor unit 190m Note 1 Assume eqivalent pipe length of REFNET joint to be 0 5m that of REFNET header to be 1m that of BSVQ100 160 to be 4m that of BSVQ250 to b...

Page 13: ...es KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H KHRP26M73H KHRP26M73HP Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C Indoor units 5 6 7 8 Example R...

Page 14: ...37 0 18 0 059 0 26 0 12 0 022 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ8 16PY1 REYQ18 20PY1 REYQ22 24PY1 REYQ26PY1 REYQ28 30PY1 REYQ32 40PY1 REYQ42PY1 REYQ44 46PY1 REYQ48PY1 3...

Page 15: ...If there exists the possibility of reversed phase lose phase momentary blackout or the power goes on and off while the prod uct is operating attach a reversed phase protection circuit locally Running...

Page 16: ...3 and N phases of the power wiring should be secured separately to the hook using the included clamp 1 The ground wiring should be bound to the power wiring using the included clamp 1 to prevent outsi...

Page 17: ...moisture might enter the piping follow belows I e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter...

Page 18: ...compressor leading insulation degradation Be sure to use the correct tools The shutoff valve is not a back seat type If forced it to open it might break the valve body When using a service port use th...

Page 19: ...When the unit is shipped from the factory the unit s internal piping is already charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant make sure to close t...

Page 20: ...rigerant flow when charging 15 Shutoff valve 16 Service port Automatic refirgerant charging operation procedure Note The marks of LED mean as follows h OFF i ON j Blinking OFF ON or Brinking 1 Open th...

Page 21: ...herwise malfunction code U3 will be displayed in the remote controller and nomal operation can not be carried out Check of shutoff valve opening Check of miswiring Judgment of piping length Check of r...

Page 22: ...customer make sure the EL COMPO BOX lid the inspection door and the unit casing are all attached 14 CAUTION FOR REFRIGERANT LEAKS Points to note in connection with refrigerant leaks Introduction The i...

Page 23: ...size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum c...

Page 24: ...English 18 NOTES...

Reviews: