Troubleshooting by Remote Controller
SiBE37-701
242
Troubleshooting
2.4
Inspection Mode
Operating the INSPECTION/TEST button on the remote controller will make it possible to
check the malfunction codes, indoor unit model codes, and outdoor unit model codes while in
inspection mode.
Inspection/test
operation
Example model
FXCQ25
FXFQ63
Example of capacity code display
Display
028
071
Product classification
VRV system
VRV system
VRV system
VRV system
Display
1
2
F
H
Indoor unit system code
System classification
(VAV indoor unit)
Outdoor air processing unit
Standard indoor unit
New ceilling suspended cassette
Indoor unit type code
Type
VRV System Inverter K Series
R-407C VRV PLUS Series
VRV Heat Recovery Series
High COP type R-407C L Series
VRV II
VRV II M/C
VRV III
Heat Pump Series
Cooling Only Series
VRV III Heat Recovery Series
Display
A A 1
A A 3
A 9 2
A A 5
A A A
A A C
A A E
A 9 E
Outdoor model code
Model
RSXYP
RXYP
RSEYP
RSXYP-L
RXYQ-M
RXYQ-MA
RXYQ-P
RXQ-P
REYQ-P
Unit
Malfunction code
Inspection
Normal display (No display)
0
L 0
Malfunction code blinks when a malfunction occurs.
Unit
Malfunction code
Inspection
Inspection mode
Push the button.
Inspection/test
operation
Push the button.
Inspection/test
operation
Push the button.
Inspection/test
operation
Push the button.
Inspection/test
operation
Push the button.
0
L 0
Indoor unit model code display
0 7 1
F C J
Outdoor unit model code display
– – –
A A 1
Test operation
Test operation mode
Capacity code
Indoor unit system code
Indoor unit type code
Progression code
0 7 1
...
F
...
C
...
J
...
(V2775)
Type
Wall mounted
2-way blow
Corner
Roundflow
Ceiling suspended
Concealed ceiling
Floor standing
Concealed ceiling (large)
Concealed floor standing type
600×600 4-way blow
Slim concealed ceiling
Display
A
C
E
F
H
J
L
P
L
6
3
Model
FXAQ
FXCQ
FXKQ
FXFQ
FXHQ
FXSQ
FXLQ
FXMQ
FXNQ
FXZQ
FXDQ
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...