Test Operation
SiBE37-701
162
Test Operation
[Shutoff Valve Operation Procedure]
When operating the shutoff valve, follow the procedure instructed below.
Note:
Do not open the shutoff valve until “1.2.1 Check work prior to turn power supply on” in page
155 are completed. If the shutoff valve is left open without turning on the power, it may cause
refrigerant to buildup in the compressor, leading insulation degradation.
Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it might break the valve body.
When using a service port, use the charge hose.
After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
The sizes of the shutoff valves on each model and the tightening torque for each size are listed
in the table below.
<Size of Shutoff Valve>
REYQ8~16PY1B
REYQ18~48P7Y1B
8HP type
10HP type
12HP type
14HP type
16HP type
Liquid pipe shutoff valve
φ
9.5
φ
12.7
The 12HP type corresponds to the 12.7-
diameter onsite piping using the accessory
pipe.
Suction gas shutoff valve
φ
25.4
The 8HP type corresponds to the 19.1-diameter onsite piping using the
accessory pipe.
The 10HP type corresponds to the 22.2-diameter onsite piping using the
accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
HP/LP gas shutoff valve
φ
19.1
The 8HP type corresponds to the 15.9-diameter onsite piping using the
accessory pipe.
The 14·16 HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
8HP type
10HP type
12HP type
14HP type
16HP type
Liquid pipe shutoff valve
φ
9.5
φ
12.7
The 12HP type corresponds to the 12.7-
diameter onsite piping using the accessory
pipe.
Suction gas shutoff valve
φ
25.4
The 8 · 10HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
HP/LP gas shutoff valve
φ
19.1
The 14 · 16 HP type corresponds to the 22.2-diameter onsite piping
using the accessory pipe.
Equalizer pipe shutoff
valve
φ
19.1
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...