Test Operation
SiBE37-701
156
Test Operation
•
Calculate a necessary additional refrigerant charging amount according to the procedure for
calculation shown below.
*
Procedure for calculating additional refrigerant charging amount (Unit: 0.1 kg)
Correction amount with indoor unit
Correction amount with a total capacity of indoor units
•
If there is a refrigerant shortage, charge a liquid refrigerant through the stop valve service
port with the stop valves of liquid and those of gas closes after the completion of vacuum
drying.
•
If the refrigerant charging is still insufficient, "turn ON the power supply" following the
information on the page 160 ~.
Check on amount of refrigerant
charge
Is a proper quantity of refrigerant charged?
The following method is available for additional charging of
refrigerant.
(1) Calculate additional refrigerant quantity.
System name
Correction
amount
Ratio of total capacity of the
connected indoor units to
the rated capacity of the
outdoor unit (A)
Correction amount
Model REYQ8-16PY1B
3.6 kg
Model REYQ18-20P7Y1B
1.0kg
Model
REYQ18 -
32P7Y1B
Model
REYQ34 -
48P7Y1B
Model REYQ22-24P7Y1B
1.5kg
+
Model REYQ26P7Y1B
2.0kg
+
Model REYQ28-30P7Y1B
2.5kg
100%<A
≤
120
%
0.5kg
Model REYQ32-40P7Y1B
3.0kg
120%<A
≤
130
%
0.5kg
1.0kg
Model REYQ42P7Y1B
3.5kg
Model REYQ44-46P7Y1B
4.0kg
Model REYQ48P7Y1B
4.5kg
R
× 1.02
Total length of
φ
22.2-mm
liquid pipe)
× 0.37
Total length of
φ
9.5-mm
liquid pipe)
× 0.059
Total length of
φ
6.4-mm
liquid pipe)
× 0.022
Total length of
φ
19.1-mm
liquid pipe)
× 0.26
Total length of
φ
12.7-mm
liquid pipe)
× 0.12
Total length of
φ
15.9-mm
liquid pipe)
× 0.18
Check the stop valves for
conditions.
Has the additional refrigerant charging amount been
recorded on the "Precautions for servicing" label?
Check to be sure the stop valves are under the following
conditions.
Liquid-pipe
stop valve
Open
Open
Open
Suction pipe
stop valve
Open
Equalizing pipe
stop valve
Dual pressure gas
pipe stop valve
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...