Field Setting
SiBE37-701
192
Test Operation
3.1.4
Setting Contents and Code No.
– VRV Indoor unit
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
VRV
system
indoor
unit
settings
Mode
No.
Note 2
Setting
Switch
No.
Setting Contents
Second Code No.(Note 3)
Details
No
01
02
03
04
10(20)
0
Filter contamination heavy/
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there is
heavy filter contamination.)
Super
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
(1)
Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200
hrs.
Approx.
100
hrs.
1
Long life filter type
Long life filter
Super long life filter
—
—
(2)
2
Thermostat sensor in remote controller
Remote
cont Body
thermostat
Only body
thermostat
Only remote
controller
thermostat
—
(3)
3
Display time to clean air filter
calculation (Set when filter sign is not
to be displayed.)
Display
No display
—
—
(4)
12(22)
0
Optional accessories output selection
(field selection of output for adaptor for
wiring)
Indoor unit
turned ON by
thermostat
—
Operation
output
Malfunction
output
(5)
1
ON/OFF input from outside (Set when
ON/OFF is to be controlled from
outside.)
Forced OFF
ON/OFF control
External
protection
device input
—
(6)
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
1°C
0.5°C
—
—
(7)
3
Air flow setting when heating
thermostat is OFF
LL
Set fan speed
—
—
(8)
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
01:0
02:1
03:2
04:3
05:4
06:5
07:6
08:7
—
5
Power failure automatic reset
Not equipped
Equipped
—
—
(9)
6
Air flow setting when Cooling
thermostat is OFF
LL
Set fan speed
—
—
(10)
13(23)
0
Setting of normal air flow
N
H
S
—
(11)
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
F (4 directions)
T (3 directions)
W (2
directions)
—
(12)
3
Operation of downward flow flap: Yes/No
Equipped
Not equipped
—
—
(13)
4
Field set air flow position setting
Draft prevention
Standard
Ceiling
Soiling
prevention
—
(14)
5
Setting of static pressure selection
Standard
High static
pressure
—
—
(15)
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
(16)
2
Direct duct connection
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.)
∗
Note 6
Not equipped
Equipped
—
—
(17)
3
Drain pump humidifier interlock
selection
Not equipped
Equipped
—
—
(18)
5
Field set selection for individual
ventilation setting by remote controller
Not equipped
Equipped
—
—
(19)
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...