Basic Control
SiBE37-701
114
Function
2.3
Electronic Expansion Valve PI Control
Main electronic expansion valve EVM control
When the outdoor unit heat exchanging is performed via the evaporator (20SA is set to ON),
this function is used to exert PI control on the electronic expansion valve (Y1E or Y3E) so that
the evaporator outlet superheated degree (SH) will become constant.
Subcooling electronic expansion valve EVT control
In order to make the maximum use of the subcool heat exchanger, this function is used to exert
PI control on the electronic expansion valve (Y2E, Y5E or Y3E) so that the evaporator-side gas
pipe superheated degree (SH) will become constant.
Refrigerant charge electronic expansion valve EVJ control
While in automatic refrigerant charge mode, this function is used to exert PI control on the
opening degree of the electronic expansion valve (Y2E or Y4E) in response to outdoor
temperature and close the valve after the completion of refrigerant charge.
For normal operation, fully open this electronic expansion valve.
2.4
Step Control of Outdoor Unit Fans
Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
*
Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
SH = Tg - Te
SH: Evaporator outlet superheated degree
(°C)
Tg : Suction pipe temperature (°C) detected
by the heat exchanger gas pipe
thermistor R2T.
Te : Low pressure equivalent saturated
temperature (°C)
SH = Tsh - Te
SH: Evaporator outlet superheated degree
(°C)
Tsh:Suction pipe temperature (°C) detected
by the subcool heat exchanger outlet
thermistor R5T
Te: Low pressure equivalent saturated
temperature (°C)
STEP No.
Fan revolutions (rpm)
Single type
Multiple type
8HP
10HP
12HP
14HP
16HP
M8
M10
M12
M14
M16
0
0
0
0
0
0
0
0
0
0/0
0/0
1
285/255
285/255
285/255
285/255
285/255
350
350
350
230/0
230/0
2
315/285
315/285
315/285
360/315
360/315
370
370
370
380/0
380/0
3
360/330
360/330
360/330
395/365
395/365
400
400
400
290/260
290/260
4
430/400
430/400
430/400
480/440
480/440
450
450
450
375/345
375/345
5
590/560
590/560
590/560
560/530
560/530
540
560
560
570/540
570/540
6
690/660
690/660
690/660
760/730
760/730
610
680
680
720/690
720/690
7
820/790
820/790
820/790
960/930
960/930
680
710
710
910/880
910/880
8
920/890
920/890
951/931
1125/1095 1155/1125
710
750
775
1091/1061 1091/1061
9
920/890
920/890
1020/990 1125/1095 1200/1170
796
821
870
1136/1106 1136/1106
Fan1/Fan2 Fan1/Fan2 Fan1/Fan2 Fan1/Fan2 Fan1/Fan2
Fan1/Fan2 Fan1/Fan2
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...