Field Setting
SiBE37-701
212
Test Operation
No.
Setting item
Description
38
Emergency
operation
(Setting for the unit
1 operation
prohibition in multi-
outdoor-unit
system)
Used to temporarily prohibit the applicable outdoor unit
from operating should there be any faulty part in multi-
outdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
39
Emergency
operation
(Setting for the unit
2 operation
prohibition in multi-
outdoor-unit
system)
40
Emergency
operation
(Setting for the unit
3 operation
prohibition in multi-
outdoor-unit
system)
41
Prevention of
minute heating
operation by
heating thermostat
OFF unit or non-
heating-operation
unit
Make this setting to shorten the BS Cool-Heat selection
control time.
However, make the setting, pay careful attention to the
following:
• If the refrigerant piping between each BS unit
connected to outdoor unit and indoor unit is not more
than 10 m in length, this setting will be enabled.
• If the refrigerant piping between BS unit and indoor unit
is long in length, refrigerant passing sounds may
become louder at the time of BS Cool-Heat selection.
• This setting shortens the Cool-Heat selection time of all
BS units provided in the same refrigerant system.
42
Setting of BS Cool-
Heat selection
control time
Make this setting to prevent a rise in room temperature
due to minute heating capacity generated by heating
thermostat OFF unit or non-heating-operation unit while
in heating operation.
• Used to prevent minute heating operation by setting
the BS unit to COOL while in heating thermostat OFF
or non-heating-operation mode.
• With the BS unit set to default, enabling the minute
heating prevention setting of outdoor unit will enable
the minute heating prevention setting of all BS units
connected to the outdoor unit. (BS unit default setting)
• To make this setting by BS unit, make a change to the
minute heating prevention setting of the BS unit. (In
this case, enable the outdoor unit setting.)
51
Set-up of master
and slave units for
multi outdoor units
Set up master and slave units for multi-connection
outdoor units.
After setting up, press the
button for
5 seconds or more.
The numbers in the "No." column represent the number of times to press
the SET (BS2) button.
BS5 (REWIRING)
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...