Specifications
SiBE37-701
48
Specifications
Wall Mounted Unit
1-1 TECHNICAL SPECIFICATIONS
FXAQ20MAVE
FXAQ25MAVE
FXAQ32MAVE
FXAQ40MAVE
FXAQ50MAVE
FXAQ63MAVE
Nominal
Capacity
Cooling
kW
2.20
2.80
3.60
4.50
5.60
7.10
Heating
kW
2.50
3.20
4.00
5.00
6.30
8.00
Power input
(Nominal)
Cooling
kW
0.016
0.022
0.027
0.020
0.027
0.050
Heating
kW
0.024
0.027
0.032
0.020
0.032
0.060
Casing
Colour
white (3.0Y8.5/0.5)
Dimensions
Unit
Height
mm
290
290
290
290
290
290
Width
mm
795
795
795
1,050
1,050
1,050
Depth
mm
230
230
230
230
230
230
Weight
Unit
kg
11
11
11
14
14
14
Heat
Exchanger
Dimensions Nr of Rows
2
2
2
2
2
2
Fin Pitch
mm
1.40
1.40
1.40
1.40
1.40
1.40
Face Area
m²
0.161
0.161
0.161
0.213
0.213
0.213
Nr of Stages
14
14
14
14
14
14
Fan
Type
Cross flow fan
Quantity
1
1
1
1
Air Flow
Rate
Cooling
High
m³/min
7.50
8.00
9.00
12.00
15.00
19.00
Low m³/min
4.50
5.00
5.50
9.00
12.00
14.00
Fan
Motor
Quantity
1
1
1
1
1
1
Model
QCL9661M
QCL9661M
QCL9661M
QCL9686M
QCL9686M
QCL9686M
Output
(high)
W
40
40
40
43
43
43
Drive
Direct drive
Refrigerant Name
R-410A
Cooling
Sound
Pressure
High
dBA
35.0
36.0
37.0
39.0
42.0
46.0
Low dBA
29.0
29.0
29.0
34.0
36.0
39.0
Piping
connections
Liquid
(OD)
Type
Flare connection
Diameter
mm
6.4
6.4
6.4
6.4
6.35
9.5
Gas
Type
Flare connection
Diameter
mm
12.7
12.7
12.7
12.7
12.7
15.9
Drain
Diameter
mm
18
18
18
18
18
18
Heat Insulation
Foamed polystyrene/polyethylene
Air Filter
Washable resin net
Refrigerant control
Electronic expansion valve
Temperature control
Microprocessor thermostat for cooling and heating
Safety devices
PC board fuse
Standard
Accessories
Standard Accessories
Installation and operation manual
Installation panel
Paper pattern for installation
Insulation tape
Clamps
Screws
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...