background image

REYQ8~16M8W1B
VRVII System air conditioner
4PW23712-1

Installation manual

18

Confirmation of the set mode

The following items can be confirmed by setting mode 1 (H1P
led is off)

Check the led indication in the field marked 

.

1

Indication of the present operation state

-

 normal

-

 abnormal

-

 under preparation or under test operation

2

Indication of COOL/HEAT selection setting

3

Indication of low noise operation state 

-

 standard operation (= factory setting)

-

 

 operation

4

Indication of power consumption limitation setting 

-

 standard operation (= factory setting)

-

 

 operation

8.4.

Test operation

Check the stop valves

In case of 5~16 type: Make sure to open the suction and
discharge gas line stop valves and the liquid line stop valve.

In case of 18~48 type: Make sure to open the oil pressure
equalizing stop valves as well.

After installation, perform the test operation.
Unless the test operation is performed, the error code "

U3

" is

shown on the remote controller and the unit cannot be operated.

Performing the test operation

1

To  protect the compressor, make sure to turn on the power
supply 6 hours before starting operation.

2

Set to setting mode 1 (H1P led is off) (refer to 

"Setting mode 1"

on page 17

).

3

Press the 

 button for 5 seconds (or longer when the

unit is at a standstill). The test operation starts when the H2P led
blinks and the remote controller indicates 

 (test operation)

and 

 (external control).

It may take 10 minutes to bring the state of refrigerant uniform
before the compressor starts, but that is not a malfunction.
The test operation is automatically carried out in cooling mode
during 15~30 minutes.
Depending on the situation, the refrigerant running sound or the
sound of a magnetic solenoid valve may rise during this
operation.
The following items are automatically checked:
-

Check for miswiring

-

Check if stop valves are open

-

Check of refrigerant charge

-

Automatic judgement of piping length

4

After the test operation (maximum 30 minutes), the unit
automatically stops. Check the operation results by the outdoor
unit led indication.

1

When set to COOL/HEAT change-over by each individual 
outdoor unit circuit (= factory setting).

2

Indication on master unit when COOL/HEAT change-over is 
carried out by outdoor system connected in multiple system-
combination.

3

Indication on slave unit when COOL/HEAT change-over is 
carried out by outdoor system connected in multiple system-
combination.

(*)

(*) This setting = factory setting.

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

1

(*)

(*)

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

2

3

L.N.O.P

L.N.O.P

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

DEMAND

DEMAND

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

NOTE

In case of 18~48 type: check the setting and the
indication results. Refer to chapter 

"Caution for

18~48 type units" on page 19

.

After turning on the power supply, the unit cannot
be started until the H2P initialisation led goes off
(maximum 12 minutes).

NOTE

When you want to terminate the test operation,
press the 

 button. The unit will keep

running for 30 seconds and then stops. During
test operation it is impossible to stop the unit with
the remote controller.

normal

abnormal

Indoor units cannot be checked individually. After the
test operation is finished, check the indoor units
individually via the remote controller.

The led indication changes during this operation, but
that is not abnormal.

Please attach the front plate of the oudoor unit in
order to prevent incorrect judgement during operation.

BS4  TEST

BS3  RETURN

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

Summary of Contents for VRV II REYQ8M8W1B

Page 1: ...NUAL REYQ8M8W1B REYQ10M8W1B REYQ12M8W1B REYQ14M8W1B REYQ16M8W1B REYQ18M REYQ20M REYQ22M REYQ24M REYQ26M REYQ28M REYQ30M REYQ32M REYQ34M REYQ36M REYQ38M REYQ40M REYQ42M REYQ44M REYQ46M REYQ48M System a...

Page 2: ...0 0 0 1000 1 50 0 1500 1500 1 2 4 5 3 5 3 3 1 722 737 80 80 765 A B 5 6 7 5 6 7 15 1 11 12 13 8 9 8 9 A B A B 1 1 2 10 14 3 4 7 15 14 7 1 2 4 5 6 7 3 7 8 9 10 11 1 5 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 2 1...

Page 3: ...15 15 F2 F2 F1 F1 A B C Q1Q2 3 2 1 1 5 5 5 4 A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 1 2 9 3 4 5 6 7 TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P F1 IN D OUT D F2 F2 F1...

Page 4: ...20 12 13 14 15 16 17 18 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 NOTES 20 REYQ8 10 REYQ12 16...

Page 5: ...e esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs...

Page 6: ...the REYQ M units Installation of the indoor units is not described in this manual Always refer to the installation manual supplied with these units for their installation REYQ8 16M8W1B VRVII System ai...

Page 7: ...dequate for servicing and the minimum space for air inlet and air outlet is available Refer to figure 1 and choose one of the possibilities In case of an installation site where only the sides A B hav...

Page 8: ...this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to provide reasonable protection against such interference Howe...

Page 9: ...refrigeration technician and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to copper refrigerant pipi...

Page 10: ...flare nuts included with the unit Using different flare nuts may cause the refrigerant to leak 5 Protection against contamination when installing pipes Take measures to prevent foreign materials like...

Page 11: ...own in the figure A or figure B Prohibited pattern Change to pattern 1 or 2 Change as shown in the figure below 3 If the piping length between the outdoor unit connecting pipe kits or between the outd...

Page 12: ...e total capacity of all the indoor units connected below the refnet header Note 250 type cannot be connected below the refnet header How to choose an outdoor branch kit needed if the outdoor unit capa...

Page 13: ...REYQ12 12 7 28 6 REYQ14 16 22 2 REYQ18 15 9 REYQ20 22 28 6 REYQ24 34 9 REYQ26 34 19 1 REYQ36 41 3 REYQ38 48 34 9 Outdoor capacity type Piping size outer diameter Normal size Size up REYQ8 10 9 5 12 7...

Page 14: ...uum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Stop valve operation procedure Introduction Confirm the sizes of the stop valves connected to...

Page 15: ...mm Flare shape 9 5 32 7 39 9 12 8 13 2 12 7 49 5 60 3 16 2 16 6 15 9 61 8 75 4 19 3 19 7 NOTE You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may fo...

Page 16: ...within 30 minutes repeat step 2 If the operation stops immediately after restart there is a possibility that the system is overcharged The refrigerant cannot be charged more than this amount 4 After...

Page 17: ...installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Therefore never inst...

Page 18: ...pped wires should be used for grounding See figure 14 See figure 20 1 Field power supply 2 Main switch 3 Earth leak detector 4 Fuse 5 Cool heat selector 6 Remote controller 7 Outdoor unit 8 BS unit 9...

Page 19: ...n of the cup washer An improper ground connection may prevent a good ground from being achieved 1 2 1 Round pressure terminal 2 Power wire Tightening torque N m M8 Power terminal block 5 5 7 3 M8 Grou...

Page 20: ...ts must be 30 m See the paragraph Fixing field line connection on page 14 A Electric wiring diagram Printed on the back of the electric box lid 1 Cut off the shaded zones before use 2 Through cover 3...

Page 21: ...switch box cover 1 when you are done Location of the dip switches leds and buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switch...

Page 22: ...ld setting For field setting For test operation For resetting the address when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the settin...

Page 23: ...ic solenoid valve may rise during this operation The following items are automatically checked Check for miswiring Check if stop valves are open Check of refrigerant charge Automatic judgement of pipi...

Page 24: ...ation to ON The indoor unit and the outdoor unit expansion valves will fully open and some solenoid valves will be turned on The H1P led is on and the remote controller indicates test operation and ex...

Page 25: ...te the smallest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calcu...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23712 1...

Reviews: