background image

 

Installation manual

17

REYQ8~16M8W1B

VRVII System air conditioner

4PW23712-1

Setting the push button switch (BS1~5)

Function of the push button switch which is located on the outdoor
unit PCB (A1P):

The figure shows state of the led indications when the unit is shipped
from the factory.

Setting the mode

The set mode can be changed with the 

 button according

to the following procedure:

For setting mode 1:  Press the 

 button once, the

H1P led is off 

.

For setting mode 2:  Press the 

 button for

5 seconds, the H1P led is on 

.

If the H1P led is blinking 

 and the 

 button is pushed

once, the setting mode will change to setting mode 1.

Setting mode 1 

(not in case of cooling only unit)

The H1P led is off (COOL/HEAT selection setting).

Setting procedure

1

Push the 

 button and adjust the led indication to either

one of the possible settings as shown below in the field marked

:

2

Push the 

 button and the setting is defined.

Setting mode 2

The H1P led is on.

Setting procedure

1

Push the 

 button according to the required function

(A~G). The led indication that matches the required function is

shown below in the field marked 

:

2

When the 

 button is pushed, the current setting is

defined.

3

Push the 

 button according to the required setting

possibility as shown below in the field marked 

.

3.1 Possible settings for function A, B, C and G are 

 (ON) or 

(OFF).

3.2 Possible settings for function D

The noise of level 3 < level 2 < level 1 (

).

3.3 Possible settings for function E and F

For function E

  (

only: the noise of level 3 < level 2

< level 1 (

).

For function F 

(

only: the power consumption of

level 3 < level 2 < level 1 (

).

4

Push the 

 button and the setting is defined.

5

When the 

 button is pushed again, the operation

starts according to the setting.

Refer to the service manual for more details and for other settings.

For changing the set mode

For field setting

For field setting

For test operation

For resetting the address when the wiring is changed or when 
an additional indoor unit is installed

NOTE

If you get confused in the middle of the setting
process, push the 

 button. Then it returns to

setting mode 1 (H1P led is off).

1

In case of COOL/HEAT setting by each individual outdoor unit 
circuit.

2

In case of COOL/HEAT setting by the master unit when outdoor 
units are connected in multiple system-combination 

(*)

(*) It is necessary to use the optional external control adapter for 

outdoor unit (DTA104A61/62). See the instruction delivered 
with the adapter.

3

In case of COOL/HEAT setting by the slave unit when outdoor 
units are connected in multiple system-combination 

(*)

.

BS2

SET

BS1

MODE

BS3

RETURN

BS4

TEST

BS5

RESET

H1P

H2P

H3P

H4P

H5P

H6P

H7P

MODE

TEST:

HWL:

IND

MASTER

SLAVE

L.N.O.P DEMAND

C/H SELECT

BS1  MODE

BS2  SET

BS3  RETURN

BS4  TEST

BS5  RESET

BS1  MODE

BS1  MODE

BS1  MODE

BS1  MODE

BS1  MODE

BS2  SET

1

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

2

3

BS3  RETURN

Possible functions

A

additional refrigerant charging operation.

B

refrigerant recovery operation/vacuuming operation. 

C

setting of high static pressure.

D

automatic low noise operation setting at nighttime.

E

low noise operation level setting (

) via the external 

control adapter.

F

power consumption limitation setting (

) via the 

external control adapter.

G

enabling function of the low noise operation level setting 
(

) and/or power consumption limitatioin setting 

(

) via the external control adapter (DTA104A61/62). 

(*)

(*) This setting = factory setting

(*)

(*) This setting = factory setting

(*)

(*) This setting = factory setting

BS2  SET

L.N.O.P

DEMAND

L.N.O.P
DEMAND

A

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

B

C

D

E

F

G

BS3  RETURN

BS2  SET

ON

OFF

ON

ON

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

OFF

OFF

(*)

(*)

1

OFF

OFF

(*)

(*)

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

1
2
3

L.N.O.P

1

DEMAND

1

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

1
2

(*)

3

BS3  RETURN

BS3  RETURN

Summary of Contents for VRV II REYQ8M8W1B

Page 1: ...NUAL REYQ8M8W1B REYQ10M8W1B REYQ12M8W1B REYQ14M8W1B REYQ16M8W1B REYQ18M REYQ20M REYQ22M REYQ24M REYQ26M REYQ28M REYQ30M REYQ32M REYQ34M REYQ36M REYQ38M REYQ40M REYQ42M REYQ44M REYQ46M REYQ48M System a...

Page 2: ...0 0 0 1000 1 50 0 1500 1500 1 2 4 5 3 5 3 3 1 722 737 80 80 765 A B 5 6 7 5 6 7 15 1 11 12 13 8 9 8 9 A B A B 1 1 2 10 14 3 4 7 15 14 7 1 2 4 5 6 7 3 7 8 9 10 11 1 5 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 2 1...

Page 3: ...15 15 F2 F2 F1 F1 A B C Q1Q2 3 2 1 1 5 5 5 4 A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 1 2 9 3 4 5 6 7 TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P F1 IN D OUT D F2 F2 F1...

Page 4: ...20 12 13 14 15 16 17 18 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 NOTES 20 REYQ8 10 REYQ12 16...

Page 5: ...e esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs...

Page 6: ...the REYQ M units Installation of the indoor units is not described in this manual Always refer to the installation manual supplied with these units for their installation REYQ8 16M8W1B VRVII System ai...

Page 7: ...dequate for servicing and the minimum space for air inlet and air outlet is available Refer to figure 1 and choose one of the possibilities In case of an installation site where only the sides A B hav...

Page 8: ...this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to provide reasonable protection against such interference Howe...

Page 9: ...refrigeration technician and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to copper refrigerant pipi...

Page 10: ...flare nuts included with the unit Using different flare nuts may cause the refrigerant to leak 5 Protection against contamination when installing pipes Take measures to prevent foreign materials like...

Page 11: ...own in the figure A or figure B Prohibited pattern Change to pattern 1 or 2 Change as shown in the figure below 3 If the piping length between the outdoor unit connecting pipe kits or between the outd...

Page 12: ...e total capacity of all the indoor units connected below the refnet header Note 250 type cannot be connected below the refnet header How to choose an outdoor branch kit needed if the outdoor unit capa...

Page 13: ...REYQ12 12 7 28 6 REYQ14 16 22 2 REYQ18 15 9 REYQ20 22 28 6 REYQ24 34 9 REYQ26 34 19 1 REYQ36 41 3 REYQ38 48 34 9 Outdoor capacity type Piping size outer diameter Normal size Size up REYQ8 10 9 5 12 7...

Page 14: ...uum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Stop valve operation procedure Introduction Confirm the sizes of the stop valves connected to...

Page 15: ...mm Flare shape 9 5 32 7 39 9 12 8 13 2 12 7 49 5 60 3 16 2 16 6 15 9 61 8 75 4 19 3 19 7 NOTE You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may fo...

Page 16: ...within 30 minutes repeat step 2 If the operation stops immediately after restart there is a possibility that the system is overcharged The refrigerant cannot be charged more than this amount 4 After...

Page 17: ...installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Therefore never inst...

Page 18: ...pped wires should be used for grounding See figure 14 See figure 20 1 Field power supply 2 Main switch 3 Earth leak detector 4 Fuse 5 Cool heat selector 6 Remote controller 7 Outdoor unit 8 BS unit 9...

Page 19: ...n of the cup washer An improper ground connection may prevent a good ground from being achieved 1 2 1 Round pressure terminal 2 Power wire Tightening torque N m M8 Power terminal block 5 5 7 3 M8 Grou...

Page 20: ...ts must be 30 m See the paragraph Fixing field line connection on page 14 A Electric wiring diagram Printed on the back of the electric box lid 1 Cut off the shaded zones before use 2 Through cover 3...

Page 21: ...switch box cover 1 when you are done Location of the dip switches leds and buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switch...

Page 22: ...ld setting For field setting For test operation For resetting the address when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the settin...

Page 23: ...ic solenoid valve may rise during this operation The following items are automatically checked Check for miswiring Check if stop valves are open Check of refrigerant charge Automatic judgement of pipi...

Page 24: ...ation to ON The indoor unit and the outdoor unit expansion valves will fully open and some solenoid valves will be turned on The H1P led is on and the remote controller indicates test operation and ex...

Page 25: ...te the smallest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calcu...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23712 1...

Reviews: