background image

 

Installation manual

11

REYQ8~16M8W1B

VRVII System air conditioner

4PW23712-1

To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.

This outdoor unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths some systems require
additional charging of refrigerant. (Refer to 

"How to calculate the

additional refrigerant to be charged" on page 8

).

Make sure to use installation tools you exclusively use on
R-410A installations to withstand the pressure and to prevent
foreign materials from mixing into the system.

Charge the refrigerant to the liquid pipe in its liquid state. Since
R-410A is a mixed refrigerant, its composition changes if
charged in a state of gas and normal system operation would no
longer be assured.

Before filling, check whether the tank has a siphon attached or
not.

Determine the weight of refrigerant to be charged additionally
referring to the item "Additional refrigerant charge" in 

"How to

calculate the additional refrigerant to be charged" on page 8

 and

fill in the amount in the "Additional refrigerant charge label"
attached to the unit.

Charging while the outdoor unit is at a standstill

After the vacuum drying is finished, charge the additional
refrigerant in its liquid state through the liquid stop valve service
port taking into account following instructions:
-

Check that gas and liquid stop valves are closed.

-

Stop the compressor and charge the specified weight of 
refrigerant.

Charging while the outdoor unit is operating

1

Completely open the suction and discharge gas line stop valves. 

In case of a 18~48 type unit, completely open the oil pressure
equalizer stop valves as well.
Valve A + B (+ C in case of a 18~48 type unit) must be left fully
closed.
Make sure the liquid line stop valve is totally shut. If it is open,
the refrigerant cannot be charged.
Charge the additional refrigerant in its liquid state through the
service port of the liquid line stop valve.

2

While the unit is at a standstill and under setting mode 2 (refer to

8.2. 

Checks before initial start-up

"Setting the mode" on

page 17

), set the required function A (additional refrigerant

charging operation) to 

 (ON). Then operation starts. The

blinking H2P led indicates test operation and the remote
controller indicates 

 (test operation) and 

 (external

control).

3

When the specified amount of refrigerant is charged, push the

 button. Then operation stops.

The operation automatically stops within 30 minutes.

If the refrigerant charge cannot be finished within 30 minutes,
repeat step 2.

If the operation stops immediately after restart, there is a
possibility that the system is overcharged.

The refrigerant cannot be charged more than this amount.

4

After the refrigerant charge hose is removed, make sure to fully
open the liquid stop valve. Otherwise the piping may burst due to
blocked liquid.

5

After the refrigerant is charged, turn on the power for the indoor
units and for the outdoor unit.

7. F

IELD

 

WIRING

7.1.

Internal wiring - Parts table

Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:

A1P-A7P................ Printed circuit board

BS1-5..................... Push button switch (mode, set, return, wiring

check, reset)

C1-4....................... Capacitor

DS1........................ Dip switch

E1HC~3HC............ Cranckcase heater

F1U........................ Fuse (250 V, 5 A, B)(A4P)

F1U,2U .................. Fuse (250 V, 10 A, B)(A1P)

F5U........................ Field fuse

H1P-8P .................. Light emitting diode (service monitor - orange)

HAP ....................... Pilot lamp (service monitor - green)

K1M~3M ................ Compressor contactor (M1C~M3C)

K1R-15R................ Magnetic relay

L1R ........................ Reactor

M1C,2C,3C ............ Motor (compressor)

M1F ....................... Motor (fan)

PS.......................... Switching power supply

Q1RP..................... Reverse phase detector

R1 .......................... Resistor (current limiting)

R3-4....................... Resistor

R10-R133 .............. Resistor (current sensor)

R1T........................ Thermistor (fin) (A2P)

R1T........................ Thermistor (air) (A1P)

R2T........................ Thermistor (suction)

R31T~33T ............. Thermistor (discharge)

How to fill a tank with a siphon attached

Fill with the tank upright.
There is a siphon tube inside, so there is no 
need to turn the tank upside-down.

Other ways of filling the tank

Fill with the tank upside-down.

If the total refrigerant cannot be charged while the outdoor
unit is at a standstill, it is possible to charge the refrigerant
by operating the outdoor unit using the refrigerant charge
function (refer to 

"Setting mode 2" on page 17

).

ON

BS3  RETURN

All field wiring and components must be installed by a
licensed electrician and must comply with relevant local
and national regulations.

The field wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.

This product's reversed phase protection detector only
works when the product started up.

The reversed phase protection detector is designed to stop
the product in the event of an abnormalities when the
product is started up.

Replace two of the three phases (L1, L2, and L3) during
reverse-phase protection circuit operation.

Reversed phase detection is not performed while the
product is operating.

If there exists the possibility of reversed phase after an
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.

Summary of Contents for VRV II REYQ8M8W1B

Page 1: ...NUAL REYQ8M8W1B REYQ10M8W1B REYQ12M8W1B REYQ14M8W1B REYQ16M8W1B REYQ18M REYQ20M REYQ22M REYQ24M REYQ26M REYQ28M REYQ30M REYQ32M REYQ34M REYQ36M REYQ38M REYQ40M REYQ42M REYQ44M REYQ46M REYQ48M System a...

Page 2: ...0 0 0 1000 1 50 0 1500 1500 1 2 4 5 3 5 3 3 1 722 737 80 80 765 A B 5 6 7 5 6 7 15 1 11 12 13 8 9 8 9 A B A B 1 1 2 10 14 3 4 7 15 14 7 1 2 4 5 6 7 3 7 8 9 10 11 1 5 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 2 1...

Page 3: ...15 15 F2 F2 F1 F1 A B C Q1Q2 3 2 1 1 5 5 5 4 A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 1 2 9 3 4 5 6 7 TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P F1 IN D OUT D F2 F2 F1...

Page 4: ...20 12 13 14 15 16 17 18 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 NOTES 20 REYQ8 10 REYQ12 16...

Page 5: ...e esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs...

Page 6: ...the REYQ M units Installation of the indoor units is not described in this manual Always refer to the installation manual supplied with these units for their installation REYQ8 16M8W1B VRVII System ai...

Page 7: ...dequate for servicing and the minimum space for air inlet and air outlet is available Refer to figure 1 and choose one of the possibilities In case of an installation site where only the sides A B hav...

Page 8: ...this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to provide reasonable protection against such interference Howe...

Page 9: ...refrigeration technician and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to copper refrigerant pipi...

Page 10: ...flare nuts included with the unit Using different flare nuts may cause the refrigerant to leak 5 Protection against contamination when installing pipes Take measures to prevent foreign materials like...

Page 11: ...own in the figure A or figure B Prohibited pattern Change to pattern 1 or 2 Change as shown in the figure below 3 If the piping length between the outdoor unit connecting pipe kits or between the outd...

Page 12: ...e total capacity of all the indoor units connected below the refnet header Note 250 type cannot be connected below the refnet header How to choose an outdoor branch kit needed if the outdoor unit capa...

Page 13: ...REYQ12 12 7 28 6 REYQ14 16 22 2 REYQ18 15 9 REYQ20 22 28 6 REYQ24 34 9 REYQ26 34 19 1 REYQ36 41 3 REYQ38 48 34 9 Outdoor capacity type Piping size outer diameter Normal size Size up REYQ8 10 9 5 12 7...

Page 14: ...uum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Stop valve operation procedure Introduction Confirm the sizes of the stop valves connected to...

Page 15: ...mm Flare shape 9 5 32 7 39 9 12 8 13 2 12 7 49 5 60 3 16 2 16 6 15 9 61 8 75 4 19 3 19 7 NOTE You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may fo...

Page 16: ...within 30 minutes repeat step 2 If the operation stops immediately after restart there is a possibility that the system is overcharged The refrigerant cannot be charged more than this amount 4 After...

Page 17: ...installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Therefore never inst...

Page 18: ...pped wires should be used for grounding See figure 14 See figure 20 1 Field power supply 2 Main switch 3 Earth leak detector 4 Fuse 5 Cool heat selector 6 Remote controller 7 Outdoor unit 8 BS unit 9...

Page 19: ...n of the cup washer An improper ground connection may prevent a good ground from being achieved 1 2 1 Round pressure terminal 2 Power wire Tightening torque N m M8 Power terminal block 5 5 7 3 M8 Grou...

Page 20: ...ts must be 30 m See the paragraph Fixing field line connection on page 14 A Electric wiring diagram Printed on the back of the electric box lid 1 Cut off the shaded zones before use 2 Through cover 3...

Page 21: ...switch box cover 1 when you are done Location of the dip switches leds and buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switch...

Page 22: ...ld setting For field setting For test operation For resetting the address when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the settin...

Page 23: ...ic solenoid valve may rise during this operation The following items are automatically checked Check for miswiring Check if stop valves are open Check of refrigerant charge Automatic judgement of pipi...

Page 24: ...ation to ON The indoor unit and the outdoor unit expansion valves will fully open and some solenoid valves will be turned on The H1P led is on and the remote controller indicates test operation and ex...

Page 25: ...te the smallest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calcu...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23712 1...

Reviews: