REYQ8~16M8W1B
VRVII System air conditioner
4PW23712-1

Installation manual

4

PRECAUTION

Block all gaps in the holes for passing out piping and wiring using
sealing material (field supply). (Small animals may enter the
machine.)

Example: passing piping out through the front

6. R

EFRIGERANT

 

PIPING

6.1.

Selection of piping material

1.

Foreign materials inside pipes (including oils for fabrication) must be
30 mg/10 m or less.

2.

Use the following material specification for refrigerant piping:

Size: determine the proper size referring to chapter

"6.3. Example of connection" on page 7

.

Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in below table.

The pipe thickness of the refrigerant piping should comply
with relevant local and national regulations. The minimal pipe
thickness for R-410A piping must be in accordance with the
table below.

3.

Make sure to use the particular branches of piping that have been
selected referring to chapter 

"6.3. Example of connection" on page 7

.

4.

In case the required pipe sizes (inch sizes) are not available, it is also
allowed to use other diameters (mm sizes), taken the following into
account:

select the pipe size nearest to the required size.

use the suitable adapters for the change-over from inch to
mm pipes (field supply).

6.2.

Connecting the refrigerant piping

1

Installation of refrigerant piping is possible as front connection or
side connection (when taken out from the bottom) as shown in
the figure.

Use R-410A to add refrigerant.

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

CAUTION TO  BE TAKEN WHEN  BRAZING
REFRIGERANT PIPING

Do not use flux when brazing copper-to-copper refrigerant
piping. (Particularly for the HFC refrigerant piping)
Therefore, use the phosphor copper brazing filler metal
(BCuP) which does not require flux.

Flux has extremely harmful influence on refrigerant piping
systems. For instance, if the chlorine based flux is used, it
will cause pipe corrosion or, in particular, if the flux
contains fluorine, it will damage the refrigerant oil.

Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or
releasing nitrogen into the piping will create large
quantities of oxidized film on the inside of the pipes,
adversely affecting valves and compressors in the
refrigerating system and preventing normal operation.)

NOTE

Installation tools:

Make sure to use installation tools (gauge manifold
charge hose, etc.) that are exclusively used for R-410A
installations to withstand the pressure and to prevent
foreign materials (e.g. mineral oils such as SUNISO
and moisture) from mixing into the system.
(The screw specifications differ for R-410A and
R-407C.)

Vacuum pump (use a 2-stage vacuum pump with a
non-return valve):

Make sure the pump oil does not flow oppositely
into the system while the pump is not working.

1 2

3 4

1

Plug the areas marked with "

".

(When the piping is routed from the front 
panel.)

2

Suction gas side piping

3

Liquid side piping

4

Discharge gas side piping

Pipe Ø 

Temper grade of piping material

15.9

O

19.1

1/2H

 O = Annealed
 1/2H = Half hard

Pipe Ø

Minimal thickness

t (mm)

Pipe Ø 

Minimal thickness

t (mm)

6.4

0.80

22.2

0.80

9.5

0.80

28.6

0.99

12.7

0.80

34.9

1.21

15.9

0.99

41.3

1.43

19.1

0.80

1

Left-side connection

2

Front connection

3

Right-side connection

1

2

3

Summary of Contents for VRV II REYQ8M8W1B

Page 1: ...NUAL REYQ8M8W1B REYQ10M8W1B REYQ12M8W1B REYQ14M8W1B REYQ16M8W1B REYQ18M REYQ20M REYQ22M REYQ24M REYQ26M REYQ28M REYQ30M REYQ32M REYQ34M REYQ36M REYQ38M REYQ40M REYQ42M REYQ44M REYQ46M REYQ48M System a...

Page 2: ...0 0 0 1000 1 50 0 1500 1500 1 2 4 5 3 5 3 3 1 722 737 80 80 765 A B 5 6 7 5 6 7 15 1 11 12 13 8 9 8 9 A B A B 1 1 2 10 14 3 4 7 15 14 7 1 2 4 5 6 7 3 7 8 9 10 11 1 5 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 2 1...

Page 3: ...15 15 F2 F2 F1 F1 A B C Q1Q2 3 2 1 1 5 5 5 4 A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 1 2 9 3 4 5 6 7 TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P F1 IN D OUT D F2 F2 F1...

Page 4: ...20 12 13 14 15 16 17 18 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 NOTES 20 REYQ8 10 REYQ12 16...

Page 5: ...e esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs...

Page 6: ...the REYQ M units Installation of the indoor units is not described in this manual Always refer to the installation manual supplied with these units for their installation REYQ8 16M8W1B VRVII System ai...

Page 7: ...dequate for servicing and the minimum space for air inlet and air outlet is available Refer to figure 1 and choose one of the possibilities In case of an installation site where only the sides A B hav...

Page 8: ...this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to provide reasonable protection against such interference Howe...

Page 9: ...refrigeration technician and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to copper refrigerant pipi...

Page 10: ...flare nuts included with the unit Using different flare nuts may cause the refrigerant to leak 5 Protection against contamination when installing pipes Take measures to prevent foreign materials like...

Page 11: ...own in the figure A or figure B Prohibited pattern Change to pattern 1 or 2 Change as shown in the figure below 3 If the piping length between the outdoor unit connecting pipe kits or between the outd...

Page 12: ...e total capacity of all the indoor units connected below the refnet header Note 250 type cannot be connected below the refnet header How to choose an outdoor branch kit needed if the outdoor unit capa...

Page 13: ...REYQ12 12 7 28 6 REYQ14 16 22 2 REYQ18 15 9 REYQ20 22 28 6 REYQ24 34 9 REYQ26 34 19 1 REYQ36 41 3 REYQ38 48 34 9 Outdoor capacity type Piping size outer diameter Normal size Size up REYQ8 10 9 5 12 7...

Page 14: ...uum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Stop valve operation procedure Introduction Confirm the sizes of the stop valves connected to...

Page 15: ...mm Flare shape 9 5 32 7 39 9 12 8 13 2 12 7 49 5 60 3 16 2 16 6 15 9 61 8 75 4 19 3 19 7 NOTE You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may fo...

Page 16: ...within 30 minutes repeat step 2 If the operation stops immediately after restart there is a possibility that the system is overcharged The refrigerant cannot be charged more than this amount 4 After...

Page 17: ...installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Therefore never inst...

Page 18: ...pped wires should be used for grounding See figure 14 See figure 20 1 Field power supply 2 Main switch 3 Earth leak detector 4 Fuse 5 Cool heat selector 6 Remote controller 7 Outdoor unit 8 BS unit 9...

Page 19: ...n of the cup washer An improper ground connection may prevent a good ground from being achieved 1 2 1 Round pressure terminal 2 Power wire Tightening torque N m M8 Power terminal block 5 5 7 3 M8 Grou...

Page 20: ...ts must be 30 m See the paragraph Fixing field line connection on page 14 A Electric wiring diagram Printed on the back of the electric box lid 1 Cut off the shaded zones before use 2 Through cover 3...

Page 21: ...switch box cover 1 when you are done Location of the dip switches leds and buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switch...

Page 22: ...ld setting For field setting For test operation For resetting the address when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the settin...

Page 23: ...ic solenoid valve may rise during this operation The following items are automatically checked Check for miswiring Check if stop valves are open Check of refrigerant charge Automatic judgement of pipi...

Page 24: ...ation to ON The indoor unit and the outdoor unit expansion valves will fully open and some solenoid valves will be turned on The H1P led is on and the remote controller indicates test operation and ex...

Page 25: ...te the smallest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calcu...

Page 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23712 1...

Reviews: