Components
Service manual
65
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
a
c
b
b
a
High pressure switch
b
Faston connector
c
High pressure switch pipe
3
Cut the high pressure switch pipe using a pipe cutter.
4
Remove the high pressure switch from the unit.
5
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
6
Heat the end of the high pressure switch pipe using an oxygen acetylene torch
and remove the high pressure switch pipe end.
7
Stop the nitrogen supply when the piping has cooled down.
8
To install the high pressure switch, see
64].
To install the high pressure switch
1
Install the high pressure switch in the correct location.
2
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
3
Wrap a wet rag around the high pressure switch and solder the high pressure
switch pipe to the high pressure switch.
a
c
b
b
a
High pressure switch
b
Faston connector
c
High pressure switch pipe