2
|
Components
Service manual
84
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
Is the correct spare part for the PCB
installed?
Action
Yes
81] of the main PCB and
continue with the next procedure.
No
Replace the main PCB, see
85].
To check the wiring of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
81].
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
145].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
81] of the PCB and
continue with the next procedure.
To check the fuse of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
81].
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
Class 20~35
a
a
a
a
Fuse