Troubleshooting by Remote Controller Display / LED Display
SiE25-110
168
Troubleshooting
Troubleshooting
Compressor inspection
Inspect according to the diagnosis
procedure for abnormal noises,
vibration, operating status, etc.
of the compressor.
Compressor overload
Inspection of the compressor
and refrigerant system is required.
YES
NO
Turn the main power supply
off, and then disconnect the
connection between the
compressor and inverter.
Is the
secondary current of
the inverter higher than
0
A (see below) for
each phase?
NO
Replace the inverter PC board.
YES
NO
Replace the inverter PC board.
YES
Is
the
inverter output
voltage generated
approximately at the same
increasing speed on each
phase after turning on
again? (
*
)
(U-V, V-W,
W-U)
*
When operating compressor with compressor output line
disconnected, the compressor stops due to malfunction after
elapsed time of 5 seconds. Therefore, check the voltage increase
for 5 seconds.
Detection value
0
Electronic thermal detection value
Continuity check in
the power
transistor (IGBT)
Is the continuity
normal?
Check No. 10
RZP71D
RZP100 ~ 140D
Cooling
Heating
Cooling
Heating
22A × 5 seconds or
13.6A (cooling), 15.1A
(heating) × 260 seconds
33A × 5 seconds or
26A × 260 seconds
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(S2593)
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...