Troubleshooting Based on Equipment Condition
SiE25-110
108
Troubleshooting
3.2
Equipment does not Operate
Applicable Model
All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Causes
Fuse blown or disorder of contact in operation circuit
Faulty operation switch or contact point
Faulty high pressure switch
Faulty magnetic switch for fan motor
Activation or fault of overcurrent relay for fan motor
Faulty overcurrent relay for compressor
Faulty compressor protection thermostat
Insufficient insulation in electric system
Faulty contact point of magnetic switch for compressor
Malfunction of compressor
Troubleshooting
Possibly faulty electric
component
Turn on power switch or replace
fuse.
If high-harmonics circuit breaker
is not used on inverter
compressor, have the circuit
breaker replaced.
Wait until power returns.
Normal. Equipment starts
operation 3 minutes later (3-min
standby).
Diagnose based on error code
on remote controller.
Normal. Equipment starts
operation 3 minutes later (3-min
standby).
Diagnose based on error code
on remote controller.
Check electric system.
Is power
switch OFF or fuse for
power switch
blown?
Is
operation lamp on
LCD remote controller
flashing?
Is
operation switch pressed
repeatedly?
Wireless
remote controller
Is operation lamp on indoor
unit signal receiving
section flashing?
Is
thermostat changed and
reset again?
Is there power failure?
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
(S2575)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...