Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
155
6.19 Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Outdoor Unit LED
Display
A
9
1
3
2
3
3
4
4
4
Applicable
Models
RZP71~140D
Method of
Malfunction
Detection
Abnormality of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
When the fan runs with speed less than a specified one for 15 seconds or more
when the fan motor running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty
connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)
Troubleshooting
Replace the outdoor unit fan motor.
Connect the connector.
Remove the foreign matter.
YES
NO
Are fan motor
connectors
disconnected?
Replace the outdoor unit fan motor.
NO
YES
Is the pulse input?
Check No. 11
Check for pulse input
for number of rotations
on the outdoor unit
PC board.
Replace the outdoor unit PC board.
YES
NO
NO
YES
Is there
any foreign matter
around the fan?
Can the fan be
easily rotated by hand?
(S2584)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...