SiE25-110
Function Details
Function and Operation
77
Note:
1. In the initial stage of operation, the same control is also provided in heating mode.
ii) During operation (compressor ON)
Note:
2. After detecting abnormal drain pan water level, if the control function determines that there is
no abnormality within 3 minutes, the error shutdown processing is not conducted.
3. Once drain pan water level abnormality is determined, the compressor does not turn on for 2
minutes after the unit is restarted even if the water level is normal.
(B) Drain pan water level detection system (float type): units other than cassette type
i) During operation startup
Note:
1. If the drain pan water level becomes normal within 1 minute and 20 seconds after the unit is
turned on, the error shutdown processing is not conducted.
If the thermostat is ON at that time, the compressor turns ON.
2. In the initial stage of operation, the same control is also provided in heating mode.
Water level abnormality
Normal
Drain pan
ON
OFF
Compressor
ON
OFF
Drain pump
Abnormal
Normal
Error processing
Note 2)
3 min
2 min
5 sec
5 min
ON operation
Note 1)
5 min
5 min
5 sec
1 min 20 sec
Water level abnormality
Normal
Drain pan
ON
OFF
Compressor
ON
OFF
Drain pump
Abnormal
Normal
Error processing
Note 1)
Note 1)
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...