SiE25-110
Specifications
Specifications
21
FHYCP (Ceiling Mounted Cassette Type: Twin System)
Notes:
1. Nominal capacities are based on the following conditions:
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Model
Indoor Units
FHYCP50DVE
×
2
FHYCP60DVE
×
2
Outdoor Units
RZP100DV1
RZP125DV1
1 Cooling Capacity
(Min.~Max.)
kW
9.7 (4.9~11.0)
12.1 (5.8~13.8)
Btu/h
33,100 (16,700~37,500)
41,300 (19,800~47,100)
kcal/h
8,300 (4,200~9,400)
10,400 (4,900~11,800)
1 Heating Capacity
(Min.~Max.)
kW
11.0 (5.5~12.6)
13.7 (5.9~15.9)
Btu/h
37,500 (18,700~43,000)
46,700 (20,100~54,200)
kcal/h
9,400 (4,700~10,800)
11,700 (5,000~13,600)
Indoor Units
FHYCP50DVE
×
2
FHYCP60DVE
×
2
Dimensions
H
×
W
×
D
mm
246
×
840
×
840
246
×
840
×
840
Coil
Type
Cross Fin Coil (Multi Louver Fins and N-hix Tubes)
Row
×
Stages
×
Fin Pitch
2
×
8
×
1.2
2
×
10
×
1.2
Face Area
m
²
0.363
0.454
Fan
Model
QTS46D14M
QTS46D14M
Type
Turbo Fan
Motor Output
W
30
30
Air Flow Rate
m
³
/min.
(H) 16 (L) 11
(H) 17 (L) 13
Air Filter
—
Resin Net (with Mold Resistant)
Machine Weight
kg
23
24
Piping
Connections
Liquid
mm
φ
9.5 (Flare)
φ
9.5 (Flare)
Gas
mm
φ
15.9 (Flare)
φ
15.9 (Flare)
Drain
mm
I. D
φ
25
×
O. D
φ
32
I. D
φ
25
×
O. D
φ
32
Remote Controller
(Option)
Wired
BRC1C61
BRC1C61
Wireless
BRC7E61W
BRC7E61W
Decoration
Panel (Option)
Model
BYCP125D-W1
BYCP125D-W1
Color
White
White
Dimensions (H
×
W
×
D)
mm
45
×
950
×
950
45
×
950
×
950
Air Filter
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Weight
kg
5.5
5.5
Outdoor Units
RZP100DV1
RZP125DV1
Color
Pale Ivory
Pale Ivory
Dimensions
H
×
W
×
D
mm
1,435
×
900
×
320
1,435
×
900
×
320
Coil
Type
Cross Fin Coil (Waffle Fins and NHi-XA Tubes)
Row
×
Stages
×
Fin Pitch
2
×
64
×
1.4
2
×
64
×
1.4
Face Area
m
²
1.598
1.598
Comp.
Model
JT100FAVD
JT100FAVD
Type
Hermetically Sealed Scroll type
Motor Output
kW
1.9
2.4
Fan
Model
P47M11F
×
2
P47M11F
×
2
Type
Propeller
Propeller
Motor Output
W
55+55
55+55
Air Flow Rate
m
³
/min.
97
102
Machine Weight
kg
119
119
Piping
Connections
Liquid
mm
φ
9.5 (Flare)
φ
9.5 (Flare)
Gas
mm
φ
19.1 (Flare)
φ
19.1 (Flare)
Drain
mm
φ
26.0 (Hole)
φ
26.0 (Hole)
Safety Devices
High Pressure Switch. Fuse.
Capacity Control
Compressor Revolution Speed Control (Inverter System)
Refrigerant Control
Expansion Valve (Electronic Type)
Ref. Piping
Max. Length
m
70 (Equivalent Length 90m)
70 (Equivalent Length 90m)
Max. Height Difference
m
30
30
Refrigerant
Model
R-407C
R-407C
Charge
kg
5.0 (Charged for 30m)
5.0 (Charged for 30m)
Ref. Oil
Model
DAPHNE FVC68D
DAPHNE FVC68D
Charge
L
1.20
1.20
Drawing No.
4D034231
Conversion Formulae
kcal/h=kW
×
860
Btu/h=kW
×
3414
cfm=m
³
/min
×
35.3
Cooling
Heating
Piping length
Hz-Volts
Indoor: 27˚CDB, 19.0˚CWB
Outdoor: 35˚CDB, 24˚CWB
Indoor: 20˚CDB, 15˚CWB
Outdoor: 7˚CDB, 6˚CWB
7.5m
(Horizontal)
50Hz~240V
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...