Function Details
SiE25-110
96
Function and Operation
4.2.27 Setting mode
Test Run Control
When carrying out cooling operation first time after installation and by pushing TEST RUN
button on the indoor unit remote controller, the unit runs for about 3 minutes in "Test Run
Mode".
When carrying out operation first time in heating mode after installation, the unit will not run
in the "Test Run Mode".
Further, when carrying out heating operation by pushing the TEST RUN button on the indoor
unit remote controller, the unit will not run in the "Test Run Mode" too. (Carries out heating
operation in forced thermostat ON.)
In the "Test Run Mode", senses on-site installation status including failure to open stop
300valves, etc. and determines malfunction immediately. When "U0" malfunction code is
displayed, check the on-site installation status for failure to open stop valves, etc.
When the malfunction code is not displayed, continues cooling operation.
(This control is carried out again when turning power on first time after refrigerant collection
by pump down switch is complete.)
Outdoor Unit Low
Noise Control
A. Setting by dip switch
[Night-time automatic low noise setting]
When setting dip switches DS1-3 on the outdoor unit PC board to ON, carries out low noise
operation by presuming the current time in accordance with changes of outside temperature
and automatically restricting the number of revolutions of outdoor unit fan and operating
frequency of compressor at night (22 to 8 o’clock). (Time at night is a target only.)
B. Setting via contact input (manual low noise setting)
When short circuit between
T
1
and
T
2
on terminal block X1M mounted on the outdoor unit PC
board, carries out low noise operation by restricting the outdoor unit fan speed and operating
frequency of compressor.
Condition
A
Condition
B
Condition
C
Indoor unit heat exchange temp.>34˚C
8
8
8
Indoor unit heat exchange temp.>Indoor unit intake temp.+17˚C
(+12˚C if outside temperature is below 5˚C)
8
8
—
Indoor unit heat exchange temp.>Indoor unit intake temp.+22˚C
(+20˚C if outside temperature is below 5˚C)
—
—
8
3 minutes elapsed after compressor startup
8
—
—
5.5 minutes elapsed after compressor startup
—
8
—
10.5 minutes elapsed after compressor startup
—
—
8
Cooling
First operation after installation
Cooling operation in test run mode
(for about 3 minutes)
Normal cooling operation
{
&
Cooling
TEST RUN button ON
Cooling operation in test run mode
(for about 3 minutes)
Cooling operation in forced
thermostat ON
{
&
Heating
First operation after installation
Normal heating operation
{
&
Heating
TEST RUN button ON
Heating operation in forced
thermostat ON
{
&
(S2570)
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...