![Daikin SkyAir Super Inverter 70 D Series Service Manual Download Page 141](http://html1.mh-extra.com/html/daikin/skyair-super-inverter-70-d-series/skyair-super-inverter-70-d-series_service-manual_4705686141.webp)
Troubleshooting by Remote Controller Display / LED Display
SiE25-110
132
Troubleshooting
Outdoor Unit
Note:
1. Possibility of open phase in power supply.
2. In RZP model, L8 is not displayed on remote controller. Please see page 167 for more detail.
Outdoor
Unit
Malfunction
Outdoor unit LED
Display
Remote
Controller
Display
Location of Malfunction
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
A
1
2
3
4
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
5 4 3 3 3
E0
—
—
Activation of protection
device Note 1.
148
5
— — — —
E1
—
—
Outdoor unit P.C board
malfunction
149
5 4 3 3 3
E3
—
—
—
Abnormality of high
pressure (HPS)
150
9 4 3 3 3
E4
—
—
Abnormality of low
pressure (outdoor)
152
9 4 3 3 3
E5
—
—
Compressor motor lock
malfunction
153
9 3 3 4 4
E7
Outdoor fan motor lock or
outdoor fan instantaneous
overcurrent malfunction
155
5 3 3 3 3
E9
—
—
Malfunction of Electronic
expansion valve
156
5 4 3 3 3
F3
—
—
Discharge pipe
temperature malfunction
158
5 4 4 3 3
H3
—
—
Faulty high pressure switch
(HPS)
160
5 4 4 3 3
H7
—
—
Malfunction of outdoor fan
signal
161
5 4 4 3 3
H9
—
—
Malfunction of outdoor air
temperature sensor system
162
5 4 4 3 3
J3
—
—
Malfunction of discharge
pipe temperature sensor
system
162
9 4 4 3 3
J5
—
—
Suction pipe thermistor
malfunction
162
5 4 4 3 3
J6
—
—
Malfunction of heat
exchanger temperature
sensor system
162
5 4 4 3 3
JC
—
—
Suction pipe pressure
sensor malfunction
163
5 3 3 3 4
L4
—
—
High temperature of
radiation fin
164
5 3 3 4 3
L5
—
—
Overcurrent of DC output
(instantaneous)
165
5 3 4 4 4
(
L8
)
Note 2
—
—
Electronic thermal switch
(time lag)
167
5 4 4 4 4
L9
—
—
Stall prevention (time lag)
169
— — — — —
LC
—
—
Malfunction of transmission
system (between control
PCB and inverter PCB)
171
9 4 3 3 4
P1
—
—
Open phase or voltage
unbalance
173
5 4 4 3 3
P4
—
—
Faulty radiation fin
temperature sensor
175,176
5
— — — —
PJ
—
—
Error in capacity setting
177
Summary of Contents for SkyAir Super Inverter 70 D Series
Page 11: ...SiE25 110 2...
Page 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Page 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Page 31: ...Specifications SiE25 110 22 Specifications...
Page 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Page 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Page 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Page 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Page 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Page 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Page 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Page 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Page 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Page 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Page 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Page 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Page 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Page 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Page 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Page 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Page 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Page 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Page 251: ...SiE25 110 iv Index...